79
Basic Data I/O Mapping
APPENDIX C
APPENDIX C
Conventional Modules
Conventional modules are provided for backward-compatibility with previous
OMRON Inverter products. Three modules are supported: Basic Data,
Extended Data 1 and Extended Data 2.
Note
Set P182 = 1 for the Option Board to support the Conventional modules
C-1
Basic Data I/O Mapping
The Torque Reference only becomes effective if: P033 = 6, A044 = 3 and ATR
is assigned to a digital input and turned on. Refer to MX2 User Manual section
3-9-4.
The Torque Reference only becomes effective if: P033 = 7. Refer to RX User
Manual section 4-3 Torque Control.
C-2
Extended Data 1 I/O Mapping
Note
The Torque Reference only becomes effective if: P033 = 6, A044
= 3 and ATR is assigned to a digital input and turned on. Refer to
MX2 User Manual section 3-9-4.
Table C-1 Basic data format I/O mapping
Word Offset
Input Area
Output Area
+0
Operation Command
*1
(Section C-4)
*1.
Refer to
section C-4 Operation Command and Inverter Status Registers
on page 80 for the Op-
eration Command and Inverter Status register definitions
Inverter Status
*1
(Section C-4)
+1
Frequency Reference
Output Frequency
+2
Torque Reference [1 %]
Output Torque [1 %]
Table C-2 Ext1 data format I/O mapping
Word Offset
Output Area
Input Area
+0
Operation Command
*1
(Section C-4)
*1.
Refer to
section C-4 Operation Command and Inverter Status Registers
on page 80 for the Op-
eration Command and Inverter Status register definitions
Inverter Status
*1
(Section C-4)
+1
Frequency Reference
Speed (Scaled Frequency)
+2
Torque Reference [1 %]
Output Torque [1 %]
+3
Torque Compensation [1 %]
Encoder Speed
+4
(Reserved)
Frequency Reference
+5
Analog Output Channel 1
Output Frequency
+6
(Reserved)
Output Current [0.1 A]
+7
Digital Outputs
Analog Input Channel 1
+8
Modbus
Message Area
(Section C-5)
Instruction
Modbus
Message Area
(Section C-5)
Result
+9
+10
Data
Data
+11
+12
+13
+14
(Unused)
(Unused)
+15
Control
Status
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 79 Donnerstag, 8. September 2011 11:53 11
Содержание 3G3AX-MX2-PRT-E
Страница 1: ...MX2 RX PROFIBUS Option Board Model 3G3AX MX2 PRT E 3G3AX RX PRT E USER S Manual Cat No I111E EN 02...
Страница 6: ...vi...
Страница 14: ...xiv Compliance with EC Directives...
Страница 20: ...6 Introduction to PROFIBUS Section 1 3...
Страница 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Страница 42: ...28 Configuring the Network Section 3 2...
Страница 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Страница 108: ...94 APPENDIX G...
Страница 110: ...96 APPENDIX H...
Страница 113: ...97...
Страница 115: ......