78
Parameter Processing Message Area - PKW
APPENDIX B
B-4
Parameter Processing Message Area - PKW
The PKW Message Area provides an interface to read and change Inverter or
Option Board parameters using the I/O Data Exchange area. Several tasks
support reading and changing different parameter types and sizes. A failed
task is accompanied by error code detail to simplify diagnosis.
Table B-3 PPO format PKW mapping
Word
Offset
Con-
tents
Bit Definitions
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
+0
PKE
AK
SPM
PNU
+1
IND
IND
PNU
, OR
(Unused)
IND
group
+2
PWE
High word of value
+3
Low word of value or Error number
AK
Task ID (Output Area):
0
: Clear the input message area
6
: Read element value in array
1
: Read parameter value
7
: Change WORD element value in array
2
: Change WORD parameter value
8
: Change DWORD element value in array
3
: Change DWORD parameter value
9
: Read array size
Task Response (Input Area):
0
: No response
5
: Task success (DWORD element)
1
: Task success (WORD parameter)
6
: Task success (Array size)
2
: Task success (DWORD parameter)
7
: Task failed (Parameter)
4
: Task success (WORD element)
8
: Task failed (Element)
SPM
Unused (Always 0)
PNU
Parameter number:
0
:
Reserved
1..889
: Inverter parameter (Use IND for parameter group)
890..999
:
Option Board parameter
[Appendix F]
>999
: Unsupported
IND
PNU
Index in Option Board parameter array (Only evaluated if Task ID is 6, 7 or 8):
IND
group
Inverter parameter group (Only evaluated if Task ID is 6, 7 or 8):
1
: Parm group 'A'
3
: Parm group 'C'
6
: Parm group 'F'
16
: Parm group 'P'
2
: Parm group 'b'
4
: Parm group 'd'
8
: Parm group 'H'
21
: Parm group 'U'
PWE
Parameter value (If Task Response is 1, 2, 4, 5 or 6)
Error code (If Task Response is 7 or 8): Refer to Appendix G
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 78 Donnerstag, 8. September 2011 11:53 11
Содержание 3G3AX-MX2-PRT-E
Страница 1: ...MX2 RX PROFIBUS Option Board Model 3G3AX MX2 PRT E 3G3AX RX PRT E USER S Manual Cat No I111E EN 02...
Страница 6: ...vi...
Страница 14: ...xiv Compliance with EC Directives...
Страница 20: ...6 Introduction to PROFIBUS Section 1 3...
Страница 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Страница 42: ...28 Configuring the Network Section 3 2...
Страница 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Страница 108: ...94 APPENDIX G...
Страница 110: ...96 APPENDIX H...
Страница 113: ...97...
Страница 115: ......