53
Flexible Mode
Section 4-6
• When selecting the device profile when configuring the Option Board
(
Step 1
of section
3-1 Configuring the Option Board
), select the Flexible
device profile by setting P182 to 2.
• When choosing the module while configuring the network (
Step 6
of sec-
tion
3-2 Configuring the Network
), select the Flexible module.
Step 2
Set parameters P160 to 1F01h to map coil data 0 as the 1st word into the out-
put process area.
Step 3
Set parameters P161 and P162 to 0001h and 0002h to map the Modbus fre-
quency reference (F001) as the 2nd and 3rd words in the output process
area.
Step 4
Set parameter P170 to 0003h to map Inverter status A as the 1st word in the
input process area.
Step 5
Set parameter P171 to 1E01h to map coil data 1 (coil no 0010h to 001Fh) into
the 2nd word in the input process area.
Step 6
Set parameters P172 and P173 to 1001h and 1002h to map the Modbus fre-
quency monitor (d001) as the 3rd and 4th words in the input process area.
Step 7
Restart the Inverter or reset the Option Board for the new settings to take
effect.
If you configured everything correctly, your output and input process areas
should have the following mapping:
Table 73 Flex Mode Output Area with Typical Configuration
Note
The operation status coil (000Fh) cannot be used in the output process area
because it is not writeable.
Table 74 Flex Mode Input Area with Typical Configuration
dec
hex
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
-
In8
*RX
In7
In6
In5
In4
In3
In2
In1
-
-
RS EXT Dir Opr
-
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Operation command
Rotation direction command
In4
External Trip
In5
Trip reset
In6
Intelligent input terminal [1]
Intelligent input terminal [2]
In8
*RX
Intelligent input terminal [4]
Intelligent input terminal [5]
Intelligent input terminal [6]
Intelligent input terminal [8]
Bit
EXT
In7
Intelligent input terminal [7]
In3
Intelligent input terminal [3]
0000
0000
0000
0
0000
0000
0000
0
0000
0000
+2
+3
0
0
0
-
-
-
0
0
Word offset
+1
+0
Coil data 0
-
+4
-
-
+9
-
+8
+5
+6
+7
Value
F001 (0001h/0002h)
0
Register
0
0000
In2
In1
0000
RS
Dir
Opr
Value
Name
dec
hex
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
ONT RNT TRQ UV IP
*RX
OTQ FA3 AL OD OL FA2 FA1 RUN - Rdy Dir
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
FA3
OTQ
UV
RNT
ONT
IP
*RX
(Refer to Inverter MX-2 Manual section B-4-2)
Operation time over
Plug-in time over
Invstat A
OL
Overload advance notice
OD
Output deviation for PID control
IP during momentary power interruption.
Is only applicable for the RX Inverter,
(Refer to Inverter RX Manual section 4-4
Communication Function)
FA1
Constant-speed reached
Undervoltage
FA2
Set frequency overreached
TRQ
Torque limited
Rdy
Inverter ready
Set frequency reached
RUN
Running
Over-torque
Dir
Rotation direction
AL
Alarm signal
-
+4
-
-
+9
-
+8
+5
+7
-
Value
+6
+2
+3
Coil data 1
Register
Word offset
+1
+0
Invstat A
d001 (1001h/1002h)
0
0000
-
0
0
0
0002
0000
0000
0000
0000
0000
0000
0
0
Value
0
Name
0
Bit
2
0002
0000
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 53 Donnerstag, 8. September 2011 11:53 11
Содержание 3G3AX-MX2-PRT-E
Страница 1: ...MX2 RX PROFIBUS Option Board Model 3G3AX MX2 PRT E 3G3AX RX PRT E USER S Manual Cat No I111E EN 02...
Страница 6: ...vi...
Страница 14: ...xiv Compliance with EC Directives...
Страница 20: ...6 Introduction to PROFIBUS Section 1 3...
Страница 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Страница 42: ...28 Configuring the Network Section 3 2...
Страница 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Страница 108: ...94 APPENDIX G...
Страница 110: ...96 APPENDIX H...
Страница 113: ...97...
Страница 115: ......