42
Accessing Parameters
Section 4-5
Step 4
Storing changed parameter(s):
To store changed parameter(s) in non-vola-
tile memory, write a 1 to Option Board parameter 971:
Step 5
Resetting the Option Board:
To reset the Option Board, write a 2 followed
by a 1 to Option Board parameter 972:
Without changing AK or PNU, set PWE=1
The Option Board correctly executes the task and resets before responding.
After the PROFIBUS master has re-connected, the Option Board tries to exe-
cute the task a second time. The task fails because parameter 972 may only
be set to 1 if the current value is 2.
4-5-1-2
Accessing Inverter Parameters
When you address Inverter parameters, IND is used to select the parameter
group.
PNU represents the parameter number in that group. To address P160 for
example set IND=10h (P
@@@
) and PNU=0A0h (160).
Note
It is important to use array tasks (6, 7 or 8) when accessing Inverter parame-
ters. IND is only interpreted if the Option Board executes an array task.
Table 44 Parameter Processing Message Area-Initiating NV Store
Change WORD parameter value task
Write
Parameter number 971
Output area [hex]
2
3CB
00
00
0000
0001
Word offset
+0
+1
+2
+3
Function
AK
PNU
IND
-
PWE
Input area [hex]
1
3CB
00
00
0000
0000
Task success (WORD parameter) response
Table 45 Parameter Processing Message Area-Prepare Reset
Change WORD parameter value task
Write
Parameter number 972
Output area [hex]
2
3CC
00
00
0000
0002
Word offset
+0
+1
+2
+3
Function
AK
PNU
IND
-
PWE
Input area [hex]
1
3CC
00
00
0000
0000
Task success (WORD parameter) response
Table 46 Parameter Processing Message Area-Initiate Reset
Change WORD parameter value task
Write
Parameter number 972
Output area [hex]
2
3CC
00
00
0000
0001
Word offset
+0
+1
+2
+3
Function
AK
PNU
IND
-
PWE
Input area [hex]
7
3CC
00
00
0000
0011
Task failed (Parameter) response
Error: Not allowed due to operating state
Table 47 IND Values and Parameter Groups for Parameter Processing
Parameter
IND
Parameter
IND
Parameter
IND
Parameter
IND
A
@@@
01h
C
@@@
03h
F
@@@
06h
P
@@@
10h
b
@@@
02h
d
@@@
04h
H
@@@
08h
U
@@@
15h
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 42 Donnerstag, 8. September 2011 11:53 11
Содержание 3G3AX-MX2-PRT-E
Страница 1: ...MX2 RX PROFIBUS Option Board Model 3G3AX MX2 PRT E 3G3AX RX PRT E USER S Manual Cat No I111E EN 02...
Страница 6: ...vi...
Страница 14: ...xiv Compliance with EC Directives...
Страница 20: ...6 Introduction to PROFIBUS Section 1 3...
Страница 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Страница 42: ...28 Configuring the Network Section 3 2...
Страница 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Страница 108: ...94 APPENDIX G...
Страница 110: ...96 APPENDIX H...
Страница 113: ...97...
Страница 115: ......