24
Configuring the Option Board
Section 3-1
Step 4
Registers A001 and A002 are used by the Inverter to adjust the frequency
source and control source. If the second motor parameter set is used, regis-
ters A201 and A202 also have to be set. Adjust these in accordance with the
following table:
Step 5
Registers P033, P036, C021, C022 and C028 are used by the Inverter to
adjust some Inverter function sources. If required (refer to usage examples),
adjust these in accordance with the following table:
Apply the source selection parameters according the following table for the
MX2 Option Board.
P045
Action on Network
Error
Set to 0 for inverter trip
Set to 1 for deceleration and trip
Set to 2 for no action
Set to 3 for stop due to free-run
Set to 4 for deceleration and stop
P181
Output Data Keep
Mode
Define behavior if PROFIBUS master indicates
CLEAR mode or if a network error occurs:
Set to 0 for clearing all output data (stop inverter)
Set to 1 for keeping output data (inverter continues
operating)
Table 9 Configuration of PROFIBUS parameters (continued)
Param
Description
Setting
Table 10 Configuration of Inverter source selection parameters
Param
Description
Setting
A001
Motor 1
Frequency Source
For option board as source:
Set to 3 if P182 equals 2
Set to 4 if P182 equals 0 or 1
Set to 5 if P182 equals 0 or 1
A201
Motor 2
Frequency Source
A002
Motor 1 Run
Command Source
A202
Motor 2 Run
Command Source
Table 11 Configuration of Source selection MX2 parameters
Param
Description
Setting
P033
Torque Command
Source
For Option Board as source:
Set to 6 (Use Option Board register) if P182
equals 1
Set to 3 (Use P034) if P182 equals 0 or 2
P036
Torque Bias Mode
For Option Board as source:
Set to 5 (Bias set by Option Board) if P182
equals 1
Set to 0 (Bias according to sign) or 1 (Bias accord-
ing to rotation direction) if P182 equals 0 or 2
C021
Output Terminal 11
Source
Set to 63 for Option Board as source
C022
Output Terminal 12
Source
Set to 63 for Option Board as source
C026
Alarm Relay Output
Terminal Source
Set to 63 for Option Board as source (Optional)
C028
Analog Output AM
Source
Set to 16 for Option Board as source
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 24 Donnerstag, 8. September 2011 11:53 11
Содержание 3G3AX-MX2-PRT-E
Страница 1: ...MX2 RX PROFIBUS Option Board Model 3G3AX MX2 PRT E 3G3AX RX PRT E USER S Manual Cat No I111E EN 02...
Страница 6: ...vi...
Страница 14: ...xiv Compliance with EC Directives...
Страница 20: ...6 Introduction to PROFIBUS Section 1 3...
Страница 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Страница 42: ...28 Configuring the Network Section 3 2...
Страница 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Страница 108: ...94 APPENDIX G...
Страница 110: ...96 APPENDIX H...
Страница 113: ...97...
Страница 115: ......