23
Configuring the Option Board
Section 3-1
SECTION 3
Configuring Drive Parameters and Option Board
3-1
Configuring the Option Board
All Option Board parameters are stored in the Inverter. This allows for easy
replacement of the Option Board without the need to re-configure. After con-
necting the Option Board to an Inverter for the first time however, proceed with
the following steps:
Step 1
The Option Board supports 3 device profiles. Each device profile supports a
subset of the modules listed in the GSD file. The device profile is selected
using Inverter parameter P182. Use the Inverter keypad to adjust P182 to
select the device profile and supported modules.
Step 2
It is recommended to set C102 = 3 to prevent the Inverter reset input and
Stop/reset button from interfering with Option Board during operation (Setting
C102 to another value causes the Option Board to reset when a trip condition
is cleared). Use the Inverter keypad to set C102 to 3.
Step 3
Inverter registers P180, P044, P045 and P181 configure the PROFIBUS net-
work-related parameters. Adjust these to configure the node address, CLEAR
mode behavior and required action when a Fieldbus failure occurs.
Table 7 Configuration of device profile
P182
Device Profile
Supported Modules
0
(default)
PROFIdrive
[Appendix B]
PPO Type 1 (4 words PKW + 2 words PZD)
PPO Type 2 (4 words PKW + 6 words PZD)
PPO Type 3 (2 words PZD)
PPO Type 4 (6 words PZD)
PPO Type 5 (4 words PKW + 10 words PZD)
1
Conventional
[Appendix C]
Basic Data
Extended Data 1
Extended Data 2
2
Flexible
[Appendix D]
Flexible (10 words output and input)
Table 8 Configuration of Inverter Reset Mode Selection
Param
Description
Setting
C102
Reset mode selection Recommended to set to 3 (Reset mode selection
resets trip only, not Option Board)
Table 9 Configuration of PROFIBUS parameters
Param
Description
Setting
P180
PROFIBUS Node
Address
0 to 125, 0 (default) means node address 126
P044
Network Error Timer
Time to wait after a network error occurs before
executing action in P045:
0 to 9999 in 0.1 s units
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 23 Donnerstag, 8. September 2011 11:53 11
Содержание 3G3AX-MX2-PRT-E
Страница 1: ...MX2 RX PROFIBUS Option Board Model 3G3AX MX2 PRT E 3G3AX RX PRT E USER S Manual Cat No I111E EN 02...
Страница 6: ...vi...
Страница 14: ...xiv Compliance with EC Directives...
Страница 20: ...6 Introduction to PROFIBUS Section 1 3...
Страница 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Страница 42: ...28 Configuring the Network Section 3 2...
Страница 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Страница 108: ...94 APPENDIX G...
Страница 110: ...96 APPENDIX H...
Страница 113: ...97...
Страница 115: ......