Troubleshooting using the LED indicators
Section 5-1
Tip
Do not clear the trip before you are finished troubleshooting an error. When
you clear the trip, the error code is cleared from the four-digit display. The trip
history can however be read back using d080 through d086. This will allow
you to diagnose the error even if you accidentally cleared the trip cause.
5-1-2
Option board or inverter errors
During the Initialization process the RUN indicator will remain OFF. Once the
initialization has been completed correctly, the RUN indicator will be ON and
the ERR indicator OFF. The table below shows the indicator and display pat-
terns caused by Option Board or Inverter Errors.
Table 79 Option board or inverter errors
MX2
Display &
Indicators
RX
Display &
Indicators
Possible Cause(s)
Corrective Action
The Inverter does not power up.
Follow the instruction provided in
the MX2-Inverter user's manual
section 6-1-4 to troubleshoot.
Follow the instruction provided in
the RX-Inverter user's manual sec-
tion 6-1 to troubleshoot.
The Option Board is not mounted properly.
Check that the Option Board is mounted
properly and restart the Inverter.
The Option Board connector is damaged.
Replace the Option Board.
The Inverter RS input is ON.
Switch the Inverter RS input OFF.
The Option Board encountered a fatal error
during Operation.
Check that the Option Board is mounted
properly and restart the Option Board. If the
problem persists, replace the Option Board.
The Inverter does not support an Option
Board (Refer to
1-1-2 Inverter Support
)
Replace the Inverter.
The Option Board connector is damaged
Replace the Option Board.
The Inverter encountered a fatal error during
Operation.
Restart the Inverter. If the problem persists,
replace the Inverter.
The Option Board node address
was set using the set-slave address
functionality of your PROFIBUS
master or diagnostic tool, but the
Inverter password function is set.
Restart the Option Board. If you
need to set the Option Board node
address, first clear the Inverter
password (Refer to section 3-6-25
in the MX2 Inverter user's manual).
The user program requested a trip by setting
the external trip bit of the conventional mod-
ule operation command.
Check and correct all items in accordance
with the user program.
I111E-EN-02+3G3AX-MX2-RX-PRT+OperManual.book Seite 58 Donnerstag, 8. September 2011 11:53 11
Содержание 3G3AX-MX2-PRT-E
Страница 1: ...MX2 RX PROFIBUS Option Board Model 3G3AX MX2 PRT E 3G3AX RX PRT E USER S Manual Cat No I111E EN 02...
Страница 6: ...vi...
Страница 14: ...xiv Compliance with EC Directives...
Страница 20: ...6 Introduction to PROFIBUS Section 1 3...
Страница 36: ...22 How to mount the Option Board on the Inverter Section 2 3...
Страница 42: ...28 Configuring the Network Section 3 2...
Страница 70: ...56 Limitations Caused by Inverter Mode and Rating Selection Section 4 7...
Страница 108: ...94 APPENDIX G...
Страница 110: ...96 APPENDIX H...
Страница 113: ...97...
Страница 115: ......