5 CiA402 Drive Profile
5 - 22
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
5-7
Device Profile area
This chapter explains about the supported CiA402 drive profile.
•
This object gives the latest error code or warning code that occurred in the unit.
•
This object controls the state transitions of the unit.
•
Bit descriptions
•
This object gives the present state of the unit.
•
Bit descriptions
5-7-1
Drive Profile Objects
603F hex
Error code
Setting range: 0000 to FFFF hex
Unit:
Default setting: 0000 hex
Size: 2 bytes (U16)
Access: RO
PDO map: Possible
Index
Name
Data type
Specifications
603F hex
Error code
U16
0000 hex: No error
5300 hex: No response from the inverter
6331 hex: EEPROM data error
6341 hex: PDO setting error
FF00 hex: Warning occurred for the inverter
FF01 hex: Trip occurred for the inverter
6040 hex
Controlword
Setting range: 0000 to FFFF hex
Unit:
Default setting: 0000 hex
Size: 2 bytes (U16)
Access: RW
PDO map: Possible
Bit
Name
Details
0
Switch on
The state is controlled by these bits.
Quick stop is not supported. Even when the bit 2 is set to 0, it is ignored.
For details, refer to
5-1-3 Command Coding
on page 5-3.
1
Enable voltage
2
Quick stop
3
Enable operation
4 to 6
Reserved
Not used. Always keep at 0.
7
Fault reset
Faults and warnings are cleared when this bit turns ON.
8 to 15
Reserved
Not used. Always keep at 0.
6041 hex
Statusword
Setting range: 0000 to FFFF hex
Unit:
Default setting: 0000 hex
Size: 2 bytes (U16)
Access: RO
PDO map: Possible
Bit
Name
Details
0
Ready to switch on
These bits give the state.
For details, refer to
5-1-4 State Coding
on page 5-3.
1
Switched on
2
Operation enabled
3
Fault
4
Voltage enabled
5
Quick stop
6
Switch on disabled
7
Warning
0: No warning occurred for the unit or inverter.
1: Warning occurred for the unit or inverter.
8
Reserved
Not used.
9
Remote
0: Control from Controlword is disabled.
1: Indicates that control is being performed by Controlword.
10 to 15
Reserved
Not used.
All
All
All
Содержание 3G3AX-MX2-ECT
Страница 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Страница 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Страница 85: ...4 Inverter Control 4 18 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Страница 111: ...5 CiA402 Drive Profile 5 26 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...
Страница 162: ...Index 1 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT I Index ...
Страница 164: ......