3 Common Slave Specifications
3 - 6
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
3-4
Service Data Objects (SDO)
The EtherCAT Communication Unit for MX2 inverters supports SDO communications as message
communications. SDO communications are used for setting objects and monitoring the status of MX2
inverters. Objects can be set and the status monitored by reading and writing data to the entries in the
object dictionary of the Host Controller.
The following table lists the abort codes for when an SDO communications error occurs.
3-4-1
Outline
3-4-2
Abort Codes
Value
Meaning
05030000 hex
Toggle bit not changed
05040000 hex
SDO protocol timeout
05040001 hex
Client/Server command specifier not valid or unknown
05040005 hex
Out of memory
06010000 hex
Unsupported access to an object
06010001 hex
Attempt to read a write only object
06010002 hex
Attempt to write to a read only object
06020000 hex
The object does not exist in the object directory
06040041 hex
The object can not be mapped into the PDO.
06040042 hex
The number and length of the objects to be mapped would exceed the
PDO length.
06040043 hex
General parameter incompatibility reason
06040047 hex
General internal incompatibility in the device
06060000 hex
Access failed due to a hardware error
06070010 hex
Data type does not match, length of service parameter does not match
06070012 hex
Data type does not match, length of service parameter too high
06070013 hex
Data type does not match, length of service parameter too low
06090011 hex
Subindex does not exist
06090030 hex
Value range of parameter exceeded (only for write access)
06090031 hex
Value of parameter written too high
06090032 hex
Value of parameter written too low
06090036 hex
Maximum value is less than minimum value
08000000 hex
General error
08000020 hex
Data cannot be transferred or stored to the application
08000021 hex
Data cannot be transferred or stored to the application because of local control
08000022 hex
Data cannot be transferred or stored to the application because of the present
device state
08000023 hex
Object dictionary dynamic generation fails or no object dictionary is present
Содержание 3G3AX-MX2-ECT
Страница 23: ...20 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT CONTENTS ...
Страница 31: ...1 EtherCAT Network 1 8 EtherCAT Communication Unit USER S MANUAL 3G3AX MX2 ECT ...