Appendices
A-40
EtherCAT Communication Unit USER’S MANUAL (3G3AX-MX2-ECT)
Event name
PDO Setting Error
Event code
34F00000 hex
Meaning
There is an illegal setting value in the PDO mapping.
Source
EtherCAT Master Function Module
Source details
Slave
Detection
timing
At transfer of
EtherCAT Config-
uration Setup
Error attributes
Level
Minor fault
Recovery
Error reset (after
resetting slave
errors)
Log category
System
Effects
User program
Continues.
Operation
The slave can enter the Pre-operational state.
Indicators
EtherCAT NET RUN
EtherCAT NET ERR
EtherCAT LINK/ACT
---
---
---
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The PDO mapping or SyncManager
settings are incorrect.
Read and check the ALStatus code
and the value in 5200 hex. Correct the
settings.
Check that there are no mistakes in
settings for the PDO mapping and
SyncManager.
Attached