3.0 BOILER LOCATION
In all cases, the Trinity Ts must be installed indoors in a dry location where the ambient temperature must be
maintained above freezing and below 100
°
F [38
°
C]. Gas components must be protected from dripping, spraying
water, or rain during operation and servicing.
Consider the proximity of system piping, gas and electrical supply,
condensate disposal drain, and proximity to vent termination when determining the best boiler location.
Water or flood damaged components must be replaced immediately with new factory-
approved components as failure to do so may result in fire, serious injury, or death.
Boiler Area Ventilation Air Openings
If boiler area clearances are less then the recommended clearances specified in Table 3-1, the boiler area must be
ventilated. Each ventilation air opening must meet the minimum requirements of 1 in
2
per 1000 Btu/hr, but not
less then 100 in
2
. The lower ventilation opening must be located within 6” of the floor while the upper opening
must be located 6” from the top of the space.
If the "Boiler Area" does not meet the recommended clearances listed in Table 3-1, it is
considered a Closet or Alcove. In US
/
Canada, closet and alcove installations require
approved CPVC vent pipe, fittings, cements, and primers. See Table 4-3 for a list of approved materials.
Closet Installations
For closet installations, it is necessary to provide two ventilation air openings as shown in Figure 3-1, each
providing a minimum area equal to 1 in
2
per 1000 Btu/hr, but not less then 100 in
2
and within 6” of the top and
bottom of the closet door. See Table 3-1 for minimum recommended clearances.
Alcove Installations
Alcove installations have the same minimum clearances as closet installations, except the front must be
completely open to the room at a distance no greater then 18” [457 mm] from the front of the boiler and the
room is at least three (3) times the size of the alcove. Provided these conditions are met, the boiler requires no
extra ventilation air openings to the space. See Table 3-1for minimum recommended clearances.
Residential Garage Installations
When installed in a residential garage, mount the boiler a minimum of 18” [457 mm] above the floor. Locate or
protect the boiler so it cannot be damaged by a moving vehicle. Check with your local authorities for other
possible regulations pertaining to the installation of a boiler in a garage.
Wall Mounting Installations
The Ts80 is provided with integrated wall mounting brackets. Refer to Figures 3-3(a) and 3-3(b) for instructions
and illustrations on wall mountings.
Table 3-1 Minimum Clearances for Installation and Service
Dimensions - inches [mm]
Model No.
Clearances
Front
Top
Left Side
Right Side
Bottom
Flue Pipe
Minimum
24 [610]
1
12 [305]
12 [305]
4 [102]
3
0
4
1
[25]
Trinity Ts80
Recommended
24 [610]
24 [610]
24 [610]
2
12 [305]
12 [305]
1 [25]
Notes:
1
6” if surface is removable allowing a minimum of 24” [610 mm] clearance (i.e. closet installation). See Ventilation Air
Opening dimensions in Figure 3-1.
2
Clearances can be as low as 12” [305 mm] so long as the sum of the right and left side clearances is 36” [914mm].
3
The gas line exits the right side; ensure adequate service clearances are maintained.
4
The field electrical connections are made at the bottom; ensure adequate service clearances are maintained.
Closet/alcove installations in US and Canada require approved
CPVC
vent and air inlet
pipe, fittings, cements and primers (Table 4-3). Failure to follow these instructions may
result in damage or serious injury.
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...