Trinity Ts
│
Installation and Operation Instructions
Ts Series
46
Table 13-6 Setup Mode Screens
Setting
Description
Factory Settings Comments
°F/°C
Set display to Fahrenheit or Celsius; press the Up or Down
button to switch between choices
°F
LBT HOD
LOD
Enable or disable outdoor reset; press the Up or Down
button to switch between choices:
If On, proceed to Low Boiler Temperature (LBT) setting
If Off, proceed to Remote Address (Rmt Adr) setting
On
LBT
Set the Low Boiler Temperature (target temperature of water
leaving the boiler); press the Up or Down button to show the
current setting; use the Up or Down button to modify the
value as desired. Range 50°F to 95°F [10°C to 35°C].
95°F [35°C]
HOD
Set the High Outdoor Temperature (outdoor temperature
corresponding to the Low Boiler Temperature on the
Outdoor Reset Curve); press the Up or Down button to show
the current setting; use the Up or Down button to modify the
value as desired. Range 50°F to 70°F [10°C to 21°C].
70°F [21°C]
LOD
Set the Low Outdoor Temperature (outdoor temperature
corresponding to the CH setpoint on the Outdoor Reset
Curve); press the Up or Down button to show the current
setting; use the Up or Down button to modify the value as
desired. Range -40°F/C to 40°F [4°C].
0°F [-18°C]
Rmt Adr
This parameter does not apply to the Ts80 model. DO
NOT MODIFY THIS SETTING. Press the Done or Next
button to bypass.
1
LL
This parameter does not apply to the Ts80 model. DO
NOT MODIFY THIS SETTING. Press the Done or Next
button to bypass.
OFF
HS
This parameter does not apply to the Ts80 model. DO
NOT MODIFY THIS SETTING. Press the Done or Next
button to bypass.
10ºF [6ºC]
bL
This parameter does not apply to the Ts80 model. DO
NOT MODIFY THIS SETTING. Press the Done or Next
button to bypass.
70%
Do Not Adjust
Sd
Set-point value for Warm Weather Shutdown. Prevents
response to CH (Thermostat) demand calls when the outdoor
temperature is above the setting. Activate function by
adjusting down. Range 32°F-120°F [0°C-49°C].
120ºF [49ºC]
ASC
Set the Anti-Short Cycle time interval. Used to prevent rapid
burner cycling e.g. in low-load situations. Range 0 minutes
to 10 minutes.
5.0 minutes
Displayed in increments
of 0.1 minute (6
seconds)
bAC
The controller supports backup and restore of non-safety
parameters. To use this function requires installing a PIM
memory module in the controller (optional, purchased
separately).
N/A
Requires an optional
PIM memory module
PAS
Permits entry of a 3 digit passcode; press the Up or Down
button to display the entry screen; select individual digits
using the Next button; alter each digit with the Up and Down
buttons; press Done to accept.
475
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...