Trinity Ts
│
Installation and Operation Instructions
Ts Series
32
Indirect Fired Water Heater
– When installed as per Figure 10-3, the indirect fired water heater is in series
with the boiler during a demand for DHW. Therefore when using this configuration it is important to use an
Indirect Fired Water Heater that has minimal head loss. Indirect fired water heater head loss must not exceed 4’
at 4 GPM when installed as per Figure 10-3.
Figures 10-2 and 10-3 are examples of plumbing configurations using a single system circulator and multiple
system circulators, respectively.
Figure 10-2: Single System Circulator Configuration
- Often used in applications zoned with “Zone Valves”.
During a demand for central heat, the boiler energizes the System Circulator via the Central Heating (CH) pump
output (PUMP C). The System Circulator must be sized to provide adequate circulation throughout the heating
system. During a Domestic Hot Water (DHW) demand, the boiler de-energizes the System Circulator (PUMP
C) and energizes the DHW Circulator (Pump A). With this configuration the Boiler Circulator is the only pump
that causes flow through the boiler and it is powered during any demand via the boiler pump output (PUMP B).
This circulator must be sized according to Table 10-4.
The piping configuration described above requires the Central Heating system and DHW
system to be de-coupled from the “Primary Loop” via closely spaced tees (Figure 10-3).
Figure 10-3: Multiple System Circulator Configuration -
Often used in applications with “Zone Circulators”.
This configuration requires the installation of a check valve located at each circulator. During a central heating
demand the boiler energizes the Central Heat Circulator via the Central Heat pump out (PUMP C). During a
Domestic Hot Water (DHW) demand, the boiler de-energizes PUMP C and energizes the DHW Circulator
(Pump A). Both Pump A and C, used in this configuration, are responsible for water flow through the boiler and
must be sized according to Table 10-4. Pump output, PUMP B is not used in this configuration.
Figures 10-2 and 10-3 illustrate typical piping systems. These piping schematics do not
illustrate all of the required concepts and components required to have a proper
installation. Concepts not shown include: prevention of thermal-siphoning (heat traps), isolation valves, drain
and purge valves, etc. It is the responsibility of the installing contractor and system designer to determine which
system best meets the need of the installation and to consider all aspects of a proper system design. Contractor
modifications to these instructions may be required, based upon existing piping and system design.
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...