Ts Series Installation and Operation Instructions
│
Trinity Ts
5
2.0 SPECIFICATIONS
Table 2-1 Specifications
DESCRIPTION
Ts80
CSA Input Modulation
1
btu/hr [kw]
16,000-80,000
[4.7-23.4]
DOE Heating Capacity
1,2
btu/hr [kw]
73,000
[21.4]
Net I=B=R Rating
1,2
btu/hr [kw]
63,000
[18.5]
DOE AFUE
2
%
95.1
Water Connections - NPT, in.
1
Gas Connection - NPT, in.
1/2
Vent/Air-Intake
Pipe
Diameter
respectively, in. [mm]
3
3 or 4
[
76 or 102]
Vent/Air-Intake,
Max. Length, ft. [m]
105
[32]
Dimensions H x W x D
in. [mm]
28x17x12
[711x432x305]
Approx. Boiler Weight
with Water, lbs [kg]
70 [31.8]
Electrical Rating
120V
/
1Ph
/
60Hz
/
12A
Notes:
1
Listed Input and Output ratings are at minimum vent lengths at Sea Level. Numbers will be lower with longer venting
and/or altitudes greater then 2000 feet [610 m].
2
Based on rating plate input capacities, using standard test procedures prescribed by the U.S. Department of Energy.
Ratings have been confirmed by AHRI (GAMA).
3
Trinity Ts requires a special venting system, use only vent materials and methods detailed in these instructions.
Wall mounting of unit requires two people to lift the boiler into place. Failure to follow
these instructions may result in property damage or personal injury.
High Altitude Operation
The Trinity is designed to operate at its maximum listed capacity in installations less than or equal to 2000 ft
[610 m] above Sea Level. Since the density of air decreases as elevation increases, maximum specified capacity
should be de-rated for elevations above 2000 ft [610 m] in accordance with Table 2-2.
Table 2-2 De-rate % for High Altitudes
Elevations
2000 ft [610 m]
3000 ft [914 m]
4000 ft [1219 m]
4500 ft [1372 m]
5000 ft [1524 m]
In Canada
1
de-rate by 5%
de-rate by 5%
de-rate by 5%
de-rate by 5%
de-rate % may vary
In USA
2
-
de-rate by 4%
de-rate by 8%
-
de-rate by 12%
Notes:
1
Canada: Altitudes between 2000-4500 ft [610-1372 m], de-rate by 5%. Consult local authorities for de-rating capacities
for altitudes above 4500 ft [1372 m].
2
USA: De-rate capacity by 4% for every 1000 ft [305 m] over 2000 ft [610 m].
Combustion
– At elevations above 2000 feet, the combustion of the boiler must be
checked with a calibrated combustion analyzer to ensure safe and reliable operation.
It is
the Installers responsibility to check the combustion and to adjust the combustion in accordance with
Section 9.0.
Failure to follow these instructions may result in property damage, serious injury, or death.
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...