CONTROLLER AND DISPLAY
Introduction
The Controller and Display, together, form the control system of the Trinity Ts. All control configuration
parameters are stored in non-volatile memory in the Ts controller. Access to controller status and configuration is
achieved with the display; however, the controller is completely capable of operating with the display
disconnected. Controller factory settings must be field adjusted to suit the application and system requirements.
Please read the following document carefully as factory settings are not configured for a
particular application and may require adjustment in order to satisfy system requirements.
Example:
The factory setting for central heat setpoint is 180°F [82°C] which is well suited for many “low mass-
high temperature” systems; however, it should be adjusted down for “high mass-low temperature” heating
systems (i.e. 100-130
o
F for infloor heat or 130-160
o
F for cast iron radiator systems).
It is the responsibility of the installer, a licensed qualified heating technician, to configure and commission the
unit and adjust any parameters required to comply with the application and satisfy the system requirements. See
Table 13-1 for a list of the minimum parameters to be considered
/
adjusted prior to putting the unit into operation.
Table 13-1 Settings Quick Reference Table
Setting
Description
Defau Menu
Menu
Item
Central Heat
Temperature
Sets the maximum boiler target temperature for a call for central
heat (Thermostat); access via menu item “Outlet” in the User menu.
180ºF
User
(Table 13-2)
Outlet
DHW
Temperature
Sets the boiler target temperature for a call for domestic hot water
(DHW); access via menu item “DHW” in the User menu.
180ºF
User
(Table 13-2)
DHW
Low Boiler
Temperature
(LBT)
Sets the minimum boiler target temperature for a call for central
heat; temperature is achieved when outdoor reset is used and the
outdoor temperature reaches the HOD (High Out-Door temperature)
setting.
95ºF
Setup
(Tables 13-4
and 13-6)
LBT
High Out-Door
temperature
(HOD)
Sets the maximum outdoor temperature threshold; temperature
where the boiler target temperature stops decreasing with increasing
outdoor temperature, see above.
70ºF
Setup
(Tables 13-4
and 13-6)
HOD
Low Out-Door
temperature
(LOD)
Outdoor design temperature – sets the minimum outdoor
temperature; temperature where the boiler target temperature stops
increasing with decreasing outdoor temperature.
0ºF
Setup
(Tables 13-4
and 13-6)
LOD
Display Layout
Figure 13-1 Display Layout
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...