Table 16-1 Troubleshooting Chart
PROBLEM
POSSIBLE CAUSE
CORRECTIVE ACTION
Hold 63 – LCI OFF (Limit
control input)
Insufficient water pressure
Ensure pressure is at or above 15PSI; if problem
persists after exceeding 20PSI – replace low water
pressure switch (PN:83223-1)
Faulty blower
If blower remains off after the lockout is cleared,
check 120VAC supply to blower, if present
replace blower.
Blocked venting
Check for blockage of the exhaust vent.
Blocked air inlet
Check for blockage of the air inlet.
Disconnected, damaged or blocked
tubing
Inspect the clear vinyl tubing connecting the air
and – ports to the air metering elbow.
Condensation or other foreign matter may be
obstructing the tubing, preventing the switch from
sensing differential pressure caused by air flow
through the metering elbow.
Incorrect air switch setting
Contact NTI technical support.
Faulty air switch
If venting and air inlet are clear, temporarily
jumper the air switch. If the unit lights and
operates smoothly – replace air switch. If the unit
fails to light or lights but runs rough or abruptly
shuts down – check boiler internals for blockage.
WARNING
Only jumper the air switch for
diagnosing purposes.
Lockout 65 – Interrupted Air
Switch OFF
Incorrect air switch wiring
Check that the red and orange wires are connected
to quick connect tabs 3 and 1 respectively.
Incorrect air switch setting
Contact NTI technical support.
Incorrect air switch wiring
Check that the red and orange wires are connected
to quick connect tabs 3 and 1 respectively.
Hold 66 – Interrupted air
switch ON (and blower is off)
Faulty air switch
Disconnect red and orange wires from air switch
and check for open circuit between terminals 1 &
3. If continuity detected, replace air switch.
Hold 66 – Interrupted air
switch ON (and blower is on)
- Blower problem
- Faulty controller
Check low voltage wiring from blower to
controller. Check VDC signal from red–green
and black-green; if not 28-32VDC and 0 VDC
respectfully – replace controller. If signal is
correct – replace blower.
Lockout 67 – ILK OFF
External Limit Tripped
Indication that an external limit (wired to “LIM”)
had opened. Not a problem with boiler.
High Central Heat or DHW set
point.
Reduce Central Heat and DHW set points.
Hold 79 – Outlet High Limit
Insufficient water flow or pressure
See
lockout 81
below.
Lockout 81 – Delta T limit
OR
Boiler making banging or
hissing sounds
Insufficient water flow
•
Check boiler pump.
•
Ensure plumbing is correct. Check that water
pressure is at least 15PSI.
•
Boiler heat transfer surfaces may be fouled
with scale or magnetite. Clean with Fernox
DS-40 Descaler and Cleanser. See Table 10-1.
Dirty heat exchanger
Inspect and if required clean the combustion
chamber and/or heat exchanger. Refer to Section
15.0 Annual Maintenance and Inspection.
Lockout 82 – Stack limit
Faulty sensor
Check resistance of stack sensor and compare to
thermistor resistance chart, see Table 16-2.
Lockout 85 – Inlet/Outlet
Inversion Limit
Pump flowing in the wrong
direction
Ensure water circulation is flowing into the boiler
at the fitting closest to the wall.
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...