LAARS Heating Systems
Page 2
SECTION 1.
General Information
WARNING
Mascot II units
must
be installed in accordance
with the procedures detailed in this manual, or the
LAARS Heating Systems warranty will be voided.
The installation must conform to the requirements
of the local jurisdiction having authority, and, in the
United States, to the latest edition of the National Fuel
Gas Code, ANSI Z223.1/NFPA54. In Canada, the
installation must conform to the latest edition of CSA
B149.1 Natural Gas and Propane Gas Installation
Code, and/or local codes. Where required by the
authority having jurisdiction, the installation of Mascot
II boilers must conform to the Standard for Controls
and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1. Any modifications to the boiler,
its gas controls, or wiring may void the warranty.
If field conditions require modifications, consult
the factory representative before initiating such
modifications.
1.1 Introduction
This manual provides information necessary for
the installation, operation, and maintenance of LAARS
Heating Systems Mascot II appliances. Read it carefully
before installation.
All application and installation procedures
should be reviewed completely before proceeding
with the installation. Consult the LAARS Heating
Systems factory, or local factory representative, with
any problems or questions regarding this equipment.
Experience has shown that most operating problems are
caused by improper installation.
Mascot II is protected against over pressurization.
A pressure relief valve is included with each Mascot II.
The PRV should be installed prior to filling the system.
Refer to
Figures 1 and 2
for PRV locations.
IMPORTANT:
The inlet gas pressure to the appliance
must not exceed 13” W.C. (3.2kPa).
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest
Edition “National Fuel Gas Code” or 2) CSA B149.1
“Natural Gas and Propane Installation Code” and with
the requirement of the local utility or other authorities
having jurisdiction. Such applicable requirements take
precedence over the general instructions contained
herein.
All electrical wiring is to be done in accordance
with the local codes, or in the absence of local codes,
with: 1) The National Electrical Code ANSI/NFPA No.
70-latest Edition, or 2) CSA STD. C22.1 “Canadian
Electrical Code - Part 1”. This appliance must be
electrically grounded in accordance with these codes.
1.2 Model Identification
Consult the rating plate on the unit. The following
information describes the model number structure.
(1-2)
Model Series Designation
L M = Mascot II
(3)
Usage
H = Modulating Boiler
C = Combination Boiler and Water Heater
(4-6)
Size
1 2 5 = 125,000 BTU/hr input
(7)
Fuel
N = Natural Gas
P = LP Gas
(8)
Altitude
A = 0-10,000 Feet
(9)
Revision
1 = First version
(10)
Options Code
X = No Options
(11)
Pump Options
X = No Pump
(12)
Regulatory Designation
B = Internal Use
1.3 Appliance Overview
See
Figure 2
.
1.4 Warranty
LAARS Heating Systems’ Mascot II appliances
are covered by a limited warranty. The owner should
complete the warranty registration at
www.Laars.com
.
All warranty claims must be made to an authorized
Model Nomenclature
1
2
3
4
5 6
7
8
9
10
11
L
M 1
2 5
A
1
X
X
SERIES
L M
USAGE
H -
HYDRONIC
C -
COMBI
UNIT
SIZE
MBTU/h
1 2 5
FUEL
N -
NATURAL
P -
PROPANE
ALTITUDE
A -
0-10,000 FEET
REVISION
1 -
FIRST
OPTIONS
X -
NONE
PUMP
X -
NONE
REG DESIGNATION
B -
INTERNAL USE
B
12
H2338601-
Addendum to 1239 Install/Operating Instruction Manual
Addendum - Nov 16th, 2012 H2338601-
Model
Sizes
Part No.
Doc. #
Page .
Mascot ll
125
H2338600-
Doc. 1239
2
Pg 2 Model Nomenclature
An additional number has been added to the
Model Nomenclature for product tracking
purposes.
Page Change