6.0 CONDENSATE DRAIN
This unit produces liquid condensate in the heat exchanger and venting system as a product of combustion.
Steps must be taken to ensure that condensate does not collect in the venting system; therefore, all exhaust
piping must slope back to the boiler a minimum 1/4” per linear foot of vent. Condensate must be drained from
the unit into a household drain.
Check with your municipality, or local gas company to determine if the disposal of
combustion condensate is permitted in your area (e.g. in the
State of Massachusetts
the
condensate must be neutralized prior to entering a drain).
The following are important notes that must be taken into consideration when constructing the condensate drain
system (See Figure 6-1 for further details):
•
DO NOT
install condensate lines outside. A frozen or blocked drain will cause the condensate to fill the
combustion chamber. This will result in a no heat condition, as the unit will shut down, and damage to the
flame sensor, and components can occur.
•
NEVER
use copper, steel, or galvanized piping in the construction of the condensate system (condensate is
very corrosive and will corrode most metals).
•
When a condensate pump is used or required, select a pump that is designed for residential furnaces.
If the combustion chamber has been flooded due to the condensate drain backing up, or
for any other reason, the combustion chamber door must be removed and the inside of
the boiler must be inspected for component damage, e.g. the internal insulation at the front and back of the
chamber. Failure to follow these instructions may result in fire, property damage, serious injury or death.
Figure 6-1
Condensate Drain Piping
Floor Drain
Check with your local authorities
regarding disposal of condensate
(regulation may require the use of a
neutralizer).
Drain Pipe
C
onnection to the bottom of the
condensate drain tee must be made
using 1/2” Schedule 40 PVC pipe.
Secure using appropriate PVC
cement. All piping must be below
the level where the condensate
leaves the boiler.
Drain Vent
Do not block or install piping into the
top branch of the condensate drain
tee.
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...