Trinity Ts
│
Installation and Operation Instructions
Ts Series
44
Table 13-3 User Mode Screen Timeouts
Screen Displayed
Length of Inactivity that Causes Timeout
Outlet water temp
1 minute
CH water setpoint temperature
10 seconds
Inlet water temp
Delta T
DHW water temp
1 minute
DHW water setpoint temperature
10 seconds
Stack temp
Outdoor temp
Firing Rate
Lead Lag Header temperature (see Note 1)
1 minute
Lead Lag Setpoint temperature (see Note 1)
10 seconds
Note 1: Not applicable to the Ts80 model.
After the timeout period has elapsed, the display will revert to the current “home” screen in User mode, as
explained above.
Setup Mode
To enter Setup mode from User mode, press and hold both the Up and Down buttons for 5 seconds.
Entering Setup mode will force the controller to shut down the burner and enter Standby
mode. The controller will remain in this state until the “Done” button is pressed or the
inactivity timeout period elapses.
As with User mode, pressing the Next button will cause each successive screen to appear on the display.
Table
13-4 Outdoor Reset Explanation
Parameter
Description
Factory Settings Comments
Low Boiler
Temperature
(LBT)
Exiting boiler water temperature that the controller
maintains corresponding to the High Outdoor Temperature
(HOD).
Example:
If the LBT is 95°F, and the HOD setting
is 70°F, the boiler water temperature setpoint will be 95°F
when the outdoor temperature reaches 70°F. Range 50°F to
95°F [10°C to 35°C].
95°F [35°C]
High
Outdoor
Temperature
(HOD)
Outdoor temperature that corresponds to the Low Boiler
Temperature (LBT).
Example:
If the LBT is 95°F, and the
HOD setting is 70°F, the boiler water temperature setpoint
will be 95°F when the outdoor temperature reaches 70°F.
Range 50°F to 90°F [10°C to 32°C].
70°F [21°C]
Low
Outdoor
Temperature
(LOD)
Outdoor temperature that corresponds to the maximum
water temperature, or Central Heat setpoint.
Example:
If the
CH setpoint is 180°F, and the LOD setting is 0°F, the boiler
water temperature setpoint will be 180°F when the outdoor
temperature reaches 0°F. Range -40°F/C to 40°F [4°C].
0°F [-18°C]
Outdoor Design
Temperature:
- set higher for
warmer climates
- set lower for colder
climates
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...