Trinity Ts
│
Installation and Operation Instructions
Ts Series
64
Table 16-4 Alert Codes
Code
Description
Action/Response
105
Min modulation rate was invalid, % vs. RPM
106
Manual rate was invalid, % vs. RPM
107
Slow start enabled, but forced rate was invalid
108
Analog output hysteresis was invalid
109
Analog modulation output type was invalid
110
IAS open rate differential was invalid
111
IAS open step rate was invalid
112
-114
RESERVED
115
Fan was limited to its minimum duty cycle
116
Manual rate was > CH max modulation rate
117
Manual rate was > DHW max modulation rate
118
Manual rate was < min modulation rate
119
Manual rate in Standby was > absolute max rate
120
Modulation commanded rate was > CH max modulation rate
121
Modulation commanded rate was > DHW max modulation rate
122
Modulation commanded rate was < min modulation rate
123
Modulation rate was limited due to outlet limit
124
Modulation rate was limited due to Delta-T limit
125
Modulation rate was limited due to stack limit
126
Modulation rate was limited due to anti-condensation
127
Fan Speed out of range in RUN
128
Modulation rate was limited due to IAS was open
129
Slow start ramp setting of zero will result in no modulation rate change
130
No forced rate was configured for slow start ramp
131
CH demand source was invalid
132
CH P-gain was invalid
133
CH I-gain was invalid
134
CH D-gain was invalid
135
CH OFF hysteresis was invalid
136
CH ON hysteresis was invalid
137
CH sensor type was invalid
138
CH hysteresis step time was invalid
139
CH remote control parameter was invalid
140
CH ODR not allowed with remote control
141-145
RESERVED
146
CH control was suspended due to fault
147
CH header temperature was invalid
148
CH outlet temperature was invalid
149
CH steam pressure was invalid
150-156
RESERVED
157
DHW demand source was invalid
158
DHW P-gain was invalid
159
DHW I-gain was invalid
160
DHW D-gain was invalid
161
DHW OFF hysteresis was invalid
162
DHW ON hysteresis was invalid
163
DHW hysteresis step time was invalid
164
DHW sensor type was invalid
165
Inlet sensor type was invalid for DHW
Содержание TRINITY Ts80
Страница 38: ...Trinity Ts Installation and Operation Instructions Ts Series 38 Figure 11 2 Ts80 Model Low Voltage Field Wiring...
Страница 40: ...Trinity Ts Installation and Operation Instructions Ts Series 40 Figure 12 1 b Ts80 Ladder Logic Diagram...
Страница 48: ...Trinity Ts Installation and Operation Instructions Ts Series 48 Figure 13 4 Diagnostic Mode Screens...
Страница 73: ...Ts Series Installation and Operation Instructions Trinity Ts 73 NOTES...
Страница 74: ...Trinity Ts Installation and Operation Instructions Ts Series 74 NOTES...
Страница 75: ...Ts Series Installation and Operation Instructions Trinity Ts 75 NOTES...