Page 91
Version 6.0
______________________________________________________________________________
NovaTec
Mobile Gateway S20
5.1.12
Status displays of the BCU
The LEDs show the status of the BCU in two stages. The first stage is after the power on reset
of the system or after sliding the BCU into the back plane. The CPU starts an Power-On
Diagnstic with several Steps (see Picture 45). If a fault happen, the CPU stops and shows the
Error Message on the Front with the LED’s. (Ready LED flashes with 0,5 s on/off). After 3
Sekonds the CPU starts again. If the Power-On Diagnistic passes, the BCU loads the
configuration from the system and switch into the operating mode. The second stage is after the
download of the configration into the module. For both stages the following status is reported:
Picture 49:
Status displays of the BCU
BCU
Po
wer
Read
y
Reset and CPU not yet started
CPU started
Error during CPU self-test 1 (system stops)
Error during CPU self-test 2 (system stops)
CPU-Chipset initializing
Error during bootcode RAM-test (system stops)
CPU creates the stack for switching to protected mode
CPU switches to protected mode
There is not enough DRAM mounted (system stops)
BCU is ready (Ready-LED flashes slower)
Error within checksum test of the boot ROM (system stops)
(Sequentially flashing light, turning from left to right.)
Boot monitor active
Load Onboard FPGA1
Error in DRAM (system stops)
}
Ethernet connection speed indicator
Line Status indicator
Line Status indicator (Yellow)
Off
On
Flashing
Ethernet connection speed indicator (green)
Off
On
no connection
connected
Data Transfer
10 MBit
100 MBit
LED is off
LED is flashing intermittently 0,5s on / 0,5s off
LED is flashing intermittently 1s on / 1s off
LED is constantly on
Po
w
er
-O
n
D
iagn
o
sti
c