Motor force
Step-by-step
Function
Pause Time
Low
Medium
High
Open – stop – close - open
Open – stop – close - stop
Condominium operation
15 seconds
30 seconds
60 seconds
7.2.3) Level two functions (adjustable parameters)
Table 17: list of programmable functions: level two
Input LED
Parameter
LED (level)
value
Description
Adjust the motor force sensitivity to suit the type of
door. The “High” adjustment is more suitable for large
and heavy doors.
Manages the sequence of controls associated to the
Step-by-Step input or to the 1st radio command (see
tables 6 and 7).
Adjusts the pause time, namely the time which lapses
before automatic closure. This will only have an effect if
automatic closing is active
Note: “
” represents the factory setting
All the parameters can be adjusted as required without any contraindication.
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
7.2.4) Level two programming (adjustable parameters)
The adjustable parameters are factory set as shown in the table 17 with: “
” However, they can be changed at any time, as shown in Table
18. Follow the procedure carefully, as there is a maximum time of 10 seconds between pressing one key and another. If a longer period of
time lapses, the procedure will finish automatically and memorize the modifications made up to that stage.
1.
Press the key
[Set]
and hold it down (approx. 3 s)
3s
2.
Release the
[Set]
key when L1 LED starts flashing
L1
3.
Press the
[
]
keys to move the flashing LED onto the “input LED” which represents the function
which is to be changed
4.
Press the key
[Set]
and hold it down during step 5 and 6
5.
Wait approx. 3 seconds, after which the LED representing the current level of the parameter which is
to be changed will light up
6.
Press the
[
]
key to move the LED representing the value of the parameter
7.
Release the key
[Set]
8.
Wait 10 seconds before leaving the program to allow the maximum time to lapse.
10s
Note: Points 3 and 7 can be repeated during the same programming phases in order to set other parameters.
Table 18: changing the adjustable parameters
Example
SET
SET
SET
SET
7.2.5) Level one programming example (ON-OFF functions).
The sequence to follow in order to change the factory settings of the functions for activating “High speed” (L2) and “Automatic Closing” (L3).
1.
Press the key
[Set]
and hold it down (approx. 3 s)
3s
2.
Release the
[Set]
key when L1 LED starts flashing
L1
3.
Press the
[
]
key once to move the flashing LED to LED L2
L2
4.
Press the
[Set]
key once to change the status of the function associated with L2 (Motor Speed).
LED L2 will now flash with long flashes
L2
5.
Press the
[
]
key once to move the flashing LED to LED L3
L3
6.
Press the
[Set]
key once to change the status of the function associated with L3 (Automatic Closing).
LED L3 will now flash with long flashes
L3
7.
Wait 10 seconds before leaving the program to allow the maximum time to lapse.
10s
Once these operations have been completed, LEDs L1 and L3 must remain on to indicate that the “High Motor Speed” and “Automatic
Closing” functions are active.
Table 19: Level one programming
Example
SET
SET
SET
SET