Operational Testing
98
After another 3 -4 seconds, the In-Parallel sequence is completed with the low voltage
switch open. The “Export Ready” LED turns red and the site starts to generate power
and feed to the grid. During the operation, the Export ready light will be on until the
“Trip” command is given to the ClearSkyPLUS on the SEL-751 Relay.