Operational Testing
89
2. Firmly press the CLOSE button … the MV Breakers should CLOSE
3. The CLOSE button’s BREAKER CLOSED Red indicator should now be illuminated
4. The three (3) individual A-PHASE, B-PHASE, and C-PHASE Red indicators should
now also be illuminated
Numbered Illustration of Protective Relay Indicators
Manual 3-Phase Operation
While still in REPAIR SERVICE MODE, the MV VFI Breakers may be cycled OPEN and
CLOSE independent of any protection logic or recloser settings.
NOTE: Protection Logic can still cause a TRIP event. e.g. If the MV Breakers are
manually CLOSED and there is no grid voltage, the Protection Relay may still TRIP the
MV Breakers on an under voltage condition.
The following steps, demonstrate manual operation of the MV VFI Breakers for a 3-
Phase actuation:
1. Press and hold the TARGET RESET button until the TRIP Red indicator is no
longer illuminated
Содержание ClearSky Plus
Страница 16: ...Resources 16 West Terminations Side LV Cabinet West Terminations Side LV Cabinet Terminal Blocks 2 AWG Cu ...
Страница 21: ...Resources 21 ...
Страница 22: ...Resources 22 ...
Страница 28: ...Design Considerations 28 myPV ClearSky PLUS 25kV Termination Cabinet Door Swing ...
Страница 38: ...Receiving 38 Equipment is Wrapped Palletized Typically Equipment Delivery ...
Страница 45: ...Receiving 45 Top Fuse Mounting Hardware Three 3 MV Fuses Fully Assembled Installed ...
Страница 52: ...Electrical Terminations 52 LV Termination Cabinet ...
Страница 56: ...Network Integration 56 ...
Страница 64: ...Pre Energization Checks 64 View of Center Switching Cabinet Through Wire Glass Window ...
Страница 67: ...Pre Energization Checks 67 View of Three 3 PT Fuses Through Wire Glass Window ...
Страница 93: ...Operational Testing 93 Numbered Illustration of Protective Relay Indicators ...
Страница 102: ...Spare Parts 102 ...
Страница 103: ...Spare Parts 103 ...