Operational Testing
88
Numbered Illustration of Mode Selection Switch & Protective Relay Indicators
Initial Breaker Position
During the myPV ClearSky’s factory integration testing, the three (3) medium voltage
(MV)
MV) VFI breakers were left in the OPEN position by initiating a 3-Phase
command from the Protection Relay.
For the following Operational testing steps, please verify that the Mode Selection Switch
and Protection Relay indicate the following status:
1. Verify the Model Selection Switch is in the REPAIR SERVICE MODE position
2. Verify the Protection Relay indicates it is TRIPPED (Red Indication next to TRIP)
3. Verify the TRIP button’s BREAKER OPEN Green Indication is illuminated
4. Verify the SPD-TEST button’s DISABLED Yellow Indication is illuminated
Содержание ClearSky Plus
Страница 16: ...Resources 16 West Terminations Side LV Cabinet West Terminations Side LV Cabinet Terminal Blocks 2 AWG Cu ...
Страница 21: ...Resources 21 ...
Страница 22: ...Resources 22 ...
Страница 28: ...Design Considerations 28 myPV ClearSky PLUS 25kV Termination Cabinet Door Swing ...
Страница 38: ...Receiving 38 Equipment is Wrapped Palletized Typically Equipment Delivery ...
Страница 45: ...Receiving 45 Top Fuse Mounting Hardware Three 3 MV Fuses Fully Assembled Installed ...
Страница 52: ...Electrical Terminations 52 LV Termination Cabinet ...
Страница 56: ...Network Integration 56 ...
Страница 64: ...Pre Energization Checks 64 View of Center Switching Cabinet Through Wire Glass Window ...
Страница 67: ...Pre Energization Checks 67 View of Three 3 PT Fuses Through Wire Glass Window ...
Страница 93: ...Operational Testing 93 Numbered Illustration of Protective Relay Indicators ...
Страница 102: ...Spare Parts 102 ...
Страница 103: ...Spare Parts 103 ...