Protection Relay Settings
34
The myPV ClearSky PLUS routes all OPEN/TRIP and CLOSE commands through the
Protection Relay (SEL-751). The SEL-751 may be interacted with normally though the
push button interface, the SEL AcSELerator software, or via SCADA command. The
SEL-751 does not immediately CLOSE when commanded, instead it coordinates the
CLOSE event with a secondary logic device called the “RVC Controller”.
CLOSE SEQUENCE
1. CLOSE command to SEL-751 (RVC, Local, Software, SCADA, or Reclosing)
2. If ready, SEL-751 signals RVC to start automated switching sequence (maintained
signal)
3. RVC CLOSEs LV Relay Contactor (maintained coil)
4. RVC Controller verifies LV CLOSE via AUX contact.
5. After delay, RVC Controller signals SEL-751 to CLOSE MV Breaker
6. If ready, SEL-751 sends CLOSE command to MV Breaker controller
Automated Inrush Mitigation Switching
Содержание ClearSky Plus
Страница 16: ...Resources 16 West Terminations Side LV Cabinet West Terminations Side LV Cabinet Terminal Blocks 2 AWG Cu ...
Страница 21: ...Resources 21 ...
Страница 22: ...Resources 22 ...
Страница 28: ...Design Considerations 28 myPV ClearSky PLUS 25kV Termination Cabinet Door Swing ...
Страница 38: ...Receiving 38 Equipment is Wrapped Palletized Typically Equipment Delivery ...
Страница 45: ...Receiving 45 Top Fuse Mounting Hardware Three 3 MV Fuses Fully Assembled Installed ...
Страница 52: ...Electrical Terminations 52 LV Termination Cabinet ...
Страница 56: ...Network Integration 56 ...
Страница 64: ...Pre Energization Checks 64 View of Center Switching Cabinet Through Wire Glass Window ...
Страница 67: ...Pre Energization Checks 67 View of Three 3 PT Fuses Through Wire Glass Window ...
Страница 93: ...Operational Testing 93 Numbered Illustration of Protective Relay Indicators ...
Страница 102: ...Spare Parts 102 ...
Страница 103: ...Spare Parts 103 ...