9 Devices
106
Rev. 02/2018
Knocking Intensity
The
Knocking
button in the
Trends
view of the added DetCon detonation controller opens the
Knocking Intensity
view.
In this view the knocking intensity trend of all cylinders is presented. The cylinders are present-
ed in different colors and can be removed and reconnected individually from the view via the
buttons to the right next to the display window.
The areas have the following meaning:
Area
Meaning
From
to the yellow line
Reduction
The detonation controller is not registering
any excessive knocking intensity.
From the yellow line
Reduction
to the red line
Trip
The detonation controller is reducing
knocking.
From the red line
Trip
to 100
The knocking intensity is so high that the
engine must be immediately shut down.