BDV Series Gas Fireplace
VENt INStALLAtION
This fireplace must be vented to the outside. The venting system must NEVER be
attached to a chimney serving a separate solid fuel burning appliance. Each gas
appliance must use a separate vent system. Do not use common vent systems.
W
ARNING
Figure 7 - Combustible Clearances for Vent Pipe
A Minimum of 3" Clearance
to the Top Is Required Along
Horizontal Length until Flue Pipe
Penetrates Outside Wall.
W
ARNING
A Minimum 1"
Clearance to
Combustibles
Permitted All
Around Flue at
Outside Wall
Horizontal sections of this vent system require
a minimum of 3" clearances to combustibles at
the top of the flue and 1" clearance at the sides
and bottom
until the flue penetrates the outside
wall.
A minimum 1" clearance all around the
flue is acceptable at this point of penetration.
If vertical rise is 7
1
/
2
feet or higher when top
venting, the clearance to combustibles is 1" on
all sides of the horizontal run.
Vertical sections of this vent system require a
minimum of 1" clearance to combustibles on
all sides of the pipe.