background image

54D0700 

39

BDV Series Gas Fireplace

COMMAND

CENTER

4-AA BATTERY

COMPARTMENT

MASTER

SWTICH

TO JUNCTION BOX

IN FIREPLACE

CONVERSION

NG/LP

RF RECEIVER

ON/OFF BUTTON

WHITE

BLACK

WHITE

BLACK

BLACK

WHITE

GREEN

CONNECTOR

PIN TO CONTROL BOX

OPTIONAL

AC BOX

{

{

{

OPTIONAL

BLOWER

OPTIONAL

LIGHT

OPTIONAL

AUX

PLUG IN CONNECT

OR

ON/HI

OFF/LO

LED

IGNITER/SPARKER

SENSING

RED/THERMOPILE

BLACK/THERMOPILE

PILOT GAS TUBING

PILOT

CONTROL BOX

PLUG IN CONNECTOR

CONTROL BOX TO COMMAND CENTER

PLUG IN CONNECTOR

STEPPER MOTOR TO

CONTROL BOX

PLUG IN CONNECTOR

CONTROL BOX TO

SOLENOID

DC POWER/GREEN

VALVE

GROUND

INPUT 300 WATT MAX EACH

GAS IN

GAS OUT

Electrical  connections  should  only  be 

performed by a qualified, licensed electri-

cian.  Main power supply must be turned 

off  before  connecting  fans  to  the  main 

electrical  power  supply  or  performing 

service.

c

A

ut

ION

Figure 52 - Signature Command Wiring Diagram

W

A

RNING

Before installing the blower, turn off the 

fireplace and allow to cool.  Only a quali-

fied service person should service and 

repair the fireplace.  A qualified service 

person should connect and disconnect 

the fireplace to gas supply.  Follow all 

local codes.

cOMMAND cENtER WALL INStALLAtION

The command center may be mounted on the wall with the use of the SCSWEK Kit (15ft. 

cable, junction box, wall cover).
Mount the junction box provided at the desired location on the wall. Do not extend beyond 

the 15 ft. wire cable provided.
Route the wire from junction box to lower control area at bottom of fireplace. Unplug the 

12" cable from control box and command center. Plug the 15 ft. extension cable into the 

control box. Remove command center from the fireplace and plug the other end of the ex-

tension cable into the command center. Snap on wall cover provided and screw to junction 

box.

SIGNAtuRE cOMMAND - ELEctRIcAL INStALLAtION 

Содержание Direct Vent Gas Fireplace BDV300

Страница 1: ...tional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is u...

Страница 2: ...g 32 Optional Fan Blower System 33 Operating Instructions Millivolt 34 What To Do If You Smell Gas 34 Lighting Millivolt Pilot for the First Time 35 Lighting Millivolt Pilot 35 Lighting Burner 36 To Turn Off Gas 36 Operating Instructions Electronic Ignition 37 What To Do If You Smell Gas 37 Lighting Electronic Ignition 37 To Turn Off Gas 37 Check Gas Pressure Signature Command 38 Check Gas Type 38...

Страница 3: ...t properly installed by a qualified service person with glass door properly seated and sealed combustion leakage can occur CARBON MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches dizziness and or nausea If you have these signs the fireplace may not have been installed properly Get fresh air at once Have the fireplace inspected and serviced by a qual...

Страница 4: ...ppliance is installed directly on carpeting tile or other combustible material other than wood flooring you must set appliance on a metal or wood panel or hearth pad extending the full width and depth of the appliance 18 Do not use fireplace if any part has been exposed to or has been under water Immediately call a quali fied service person to arrange for replacement of the unit 19 Do not operate ...

Страница 5: ...venting system The appliance is not approved for closet or recessed installations Hi Lo Knob product SPECIFICATIONS Code Approval Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows LIST...

Страница 6: ...opane Natural Propane Max Btu hr Input 21 000 21 000 24 000 24 000 26 000 26 000 26 000 26 000 Min Btu hr Input 15 000 15 000 17 000 17 000 20 000 20 000 20 000 20 000 Orifice size 43 54 41 53 40 1 55mm 40 1 55mm Before You Start Read this homeowner manual thoroughly and follow all instructions carefully Inspect all contents for shipping damage and immediately inform your dealer if any damage is f...

Страница 7: ...directly on a combustible floor or raised on a platform of an appropriate height When the firebox is installed directly on carpeting tile or other combustible material other than wood flooring the firebox shall be installed on a metal or wood panel extending the full width and depth of the enclosure 300 400 500 600 A 331 2 371 2 411 2 471 2 B 371 4 407 8 407 8 407 8 C 281 4 291 4 331 4 391 4 D 141...

Страница 8: ...371 16 411 16 471 16 Inside Width B 297 8 32 36 42 Glass Width C 27 29 33 39 CTR Pipe D 161 2 181 2 201 2 231 2 Rear Width E 28 29 33 39 Glass Height F 18 203 8 203 8 203 8 Chassis Height G 337 8 371 2 371 2 371 2 Depth H 14 16 16 16 Height to Standoffs I 37 401 2 401 2 401 2 CTR Height J 295 8 331 8 331 8 331 8 Top Face K 21 8 11 4 11 4 11 4 Side Face L 11 2 21 2 21 2 21 2 Bottom Face M 15 16 15 ...

Страница 9: ... This fireplace may be installed along a wall across a corner or use an exterior chase See Figure 4 for suggested locations Location should be out of high traffic areas and away from furniture and draperies due to heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting...

Страница 10: ... panel extending full width and depth of the appliance WARNING clearances Clearances to combustibles mantel clearances NOTE The combustible area above the facing must not protrude more than 3 4 from the facing If it does it is considered a mantel and must meet the mantel requirements listed in this manual 12 Maximum Depth 11 Minimum 71 Minimum Minimum 4 From Both Side Walls FP2092 mantel clearance...

Страница 11: ...e two 2 wood screws or masonry concrete screws to secure fireplace to the floor Use four 4 screws to attach fireplace to framing The side nailing flanges are 1 2 or 5 8 to accommodate different wall thickness SECURING FIREPLACE to floor or framing Figure 6 Securing Fireplace to Floor and Framing Studs Framing Framing Nailing Flange Nailing Flange Screws Screws Screws Nailing Flange Nailing Flange ...

Страница 12: ... on rooftops Be aware of electrical wiring locations in walls and ceilings The following actions will void the warranty on your venting system Installation of any damaged venting component Unauthorized modification of the venting system Installation of any component part not manufactured or approved by MHSC Installation other than permitted by these instructions Finishing Material NOTE Any remote ...

Страница 13: ... Pipe Penetrates Outside Wall WARNING A Minimum 1 Clearance to Combustibles Permitted All Around Flue at Outside Wall Horizontal sections of this vent system require a minimum of 3 clearances to combustibles at the top of the flue and 1 clearance at the sides and bottom until the flue penetrates the outside wall A minimum 1 clearance all around the flue is acceptable at this point of penetration I...

Страница 14: ...e intake box and remove the cover and gasket Figure 8 4 Remove the six 6 screws securing the flue pipe to the back of the intake box and remove the pipe and gasket Figure 9 5 Replace flue pipe to top of firebox Ensure the gasket is in place and undamaged Secure with six 6 screws Figure 10 6 Place the flue pipe cover and gasket removed in Step 3 over the flue opening in back of the intake box 7 Ref...

Страница 15: ... 45 elbows up to a maximum of 270 For two story applications firestops are required at each floor level If an offset is needed in the attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installing Vent System in a Chase below If pipe is enclosed in chase it is not exposed It is very important that the vent...

Страница 16: ...mum J Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 305mm minimum K Clearance to a mechanical air supply inlet 6 1829mm minimum L Clearance above a paved sidewalk or paved driveway located on public property 7 2133mm minimum M Clearance under veranda porch deck or balcony refer to Figure 12 As specified in CSA B149 Installation Codes...

Страница 17: ... to determine the relationship between the vertical and horizontal dimensions of the vent system 1 Determine the height of the center of the horizontal vent pipe exiting through the outer wall Using this dimension on the Sidewall Vent Graph below locate the point inter secting with the slanted graph line 2 From the point of this intersection draw a vertical line to the bottom of the graph 3 Select...

Страница 18: ...rk DT outer walls are hemmed and will snap into the collar s tabs Attach Simpson s DirectVent Pro by fully insert ing into the collar and securing with self tapping screws The screws shall only penetrate the flue outer wall Refer to vent manufacturer s installation instructions to properly assemble flue 2 Locate and cut the vent opening in the wall For combustible walls first frame in opening Comb...

Страница 19: ...t cap assembly Figure 18 5 Slide the firestop over the vent pipe before connecting the horizontal run to the vent cap Figure 19 6 The termination should overlap the flue a minimum of 11 4 Apply silicone to the outer pipe termination connection Fasten termination with screws provided 7 Slide the firestop against the interior wall surface and attach with screws Figure 19 Do not recess vent terminati...

Страница 20: ...n all sides of the pipe When vent exits through foundations less than 20 below outcrop the termination must be flush up with outcropped wall above It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace or the top of the Transition Elbow to ...

Страница 21: ...nsion A plus B must not be greater than 17 5 2m The maximum number of 45 elbows permitted per side wall installation is two 2 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed in the horizontal run the length of the horizontal run MUST be reduced by 18 45cm This does not apply if the 45 elbows are installed on the vertical part of the vent system Th...

Страница 22: ...l Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approxi mately 4 below snorkel See Figure 26 3 Install vent system 4 Ensure a watertight seal is made around the vent pipe coming through the wall 5 Apply high temperature sealant caulking supplied around the 4 and 7 snorkel collars 6 Slide the snorkel into the vent pipes and secure to...

Страница 23: ...5 elbows 8 5 2 6 m 2x45 elbows 7 2 1 m A minimum of an 8 2 5 m vertical rise is required Two sets of 45 elbows offsets may be used within the vertical sections From 0 to a maxi mum of 8 2 5 m of vent pipe can be used between elbows Figure 29 The maximum angular variation allowed in the system is 270 Figure 29 1 2 3 4 1 2 3 4 FP1179 max bends FP1179 Figure 29 Maximum Elbow Usage Example Elbow 1 90 ...

Страница 24: ... from the ceiling to the position of the flue exit Mark the center point where the vent will penetrate the ceiling Drill a small locating hole a this point Drop a plumb line from the inside of the roof to the ceiling locating hole in the ceiling Mark the center point where the vent will penetrate the roof Drill a small locating hole at this point flat ceiling installation 1 Cut a 91 2 241 mm squar...

Страница 25: ...ue to add pipe sections until the height of the vent cap meets the minimum building code requirements NOTE You must increase vent height for steep roof pitches Nearby trees adjoining roof lines steep pitched roofs and other similar factors may cause poor draft or down drafting in high winds Increasing the vent height may solve this problem NOTE If the vent pipe passes through any occupied areas ab...

Страница 26: ...ce and secure with screws 2 Slide the small gear clamp over the inner flex ible vent pipe and push out of the way 3 Pull and extend the inner flexible vent 4 Slide the inner vent onto the adapter collar for a minimum 13 4 over lap 5 Locate the clamp at approximately 3 4 from the flex end and tighten 6 Secure the clamped inner section with three self tapping screws drilled equidistant just above th...

Страница 27: ...proved terminations and accessories installed per the installation instructions and Figure 36 E Installing flexible venting to horizontal termination assemblies 1 Connect the 4 flexible vent to the horizontal termination Figure 38 2 Slide termination cap adapter ring over the termination cap s outside pipe and secure with three screws 3 Connect the 7 flexible vent to the termination adapter ring F...

Страница 28: ...service person must connect appliance to gas supply Follow all local codes WARNING installation items needed Before installing fireplace and burner system make sure you have the items listed below External regulator supplied by installer Piping check local codes Sealant resistant to propane LP gas Equipment shutoff valve Test gauge connection Sediment trap recommended Tee joint Pipe wrench approve...

Страница 29: ... in supply line as shown in Figure 40 Locate sediment trap drip leg where it is within reach for cleaning Install in piping system between fuel supply and burner system Locate sediment trap drip leg where trapped matter is not likely to freeze A sediment trap collects moisture and contaminants and keeps them from going into the burner system gas controls If sediment trap drip leg is not installed ...

Страница 30: ... pressure reading be sure and turn captured screw clock wise firmly to reseal Do not over torque Check test points for gas leaks Do not use open flame to check for gas leaks WARNING FP1979 Millivolt gas valve FP1979 Figure 41 Gas Pressure Check at Gas Valve Pressure Test IN Pressure Test OUT HI LO Knob Pilot Adjustment Screw Electrical Wiring Millivolt Electrical connections should only be perform...

Страница 31: ...th this appli ance Attach the wall switch in a junction box at the desired location on the wall Figure 42 Do not extend beyond the wall switch wire length provided NOTE Extended lengths of wire may cause the fireplace not to function properly Longer length of wire is permitted if the wire is made out of larger gauge diameter wire Always check with local code Figure 42 Wiring Diagram for Wall Switc...

Страница 32: ...Wiring Do not connect 110 120 VAC to the Remote Wall Switch The appliance will malfunction WARNING Remote Wall Switch Position the wall switch Do not extend beyond the 15 feet of wire Optional DC Remote Systems These instructions replace the section entitled Hearth Mount in the Millivolt hand held remote instructions supplied with the remote 1 Plug in remote connector wire to remote receiver 2 Con...

Страница 33: ...Fan Blower Systems BLOT The junction box for the fan blower systems has been factory installed This system requires that 110 120 VAC to be wired to the factory installed junction box before the fireplace is permanently installed Figure 44 Optional Thermostatic Switch Speed Control Figure 44 Blower Wiring Diagram OPTIONAL FAN BLOWER SYSTEM ...

Страница 34: ... attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water If you do not follow these instruction exactly a fire or explosion may result causing property damage personal inju...

Страница 35: ...osed it is possible to start the lighting operation The gas control knob is designed to be operated by hand DO NOT use any tools during this operation Damaged knobs may result in serious injury WARNING 1 Depress and turn knob counterclockwise to pilot position 2 Depress fully and hold pilot gas knob Depress piezoigniterasmanytimesasneededtoignitepilot Keep knob fully depressed for a few seconds Re...

Страница 36: ...This switch allows you to turn on and to turn off the main burner without using the gas valve knob Make sure the button is in the ON position to light the main burner Figure 46 Lighting the burner Depress and turn the knob counterclockwise to the ON position Figure 47 It will take less than four 4 seconds for the burner to ignite Pilot position Depress and turn knob to pilot position to keep burne...

Страница 37: ...any part of it has been under water Immediately call a qualified ser vice technician to inspect the appliance and to replace any part of the control system and any gas control that has been under water If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life WARNING for your safety read before lighting to turn off gas Ne...

Страница 38: ...ockwise firmly to reseal Do not over torque Check test points for gas leaks Figure 51 Signature Command Valve FP1909a signature command valve alternate view 8 08 Pressure Inlet Pilot Adjust ment Screw Pressure Outlet Do not use open flame to check for gas leaks WARNING Electrical Wiring Electrical connections should only be performed by a qualified licensed electrician Main power must be off when ...

Страница 39: ... supply or performing service CAUTION figure 52 Signature Command Wiring Diagram WARNING Before installing the blower turn off the fireplace and allow to cool Only a quali fied service person should service and repair the fireplace A qualified service person should connect and disconnect the fireplace to gas supply Follow all local codes COMMAND CENTER WALL INSTALLATION The command center may be m...

Страница 40: ...ean and dry before mounting the blow er Installing the Blower 1 Remove the lower access panel by pulling up and away from unit 2 Remove glass frame by releasing the two 2 latches 500 and 600 models have three 3 latches below the firebox opening and lifting glass frame up and away from unit 3 Use the supplied Velcro on the blower and the magnetic strips to secure the blower to the firebox wall and ...

Страница 41: ...vided Figure 56 8 Plug in wiring harness to the back of AC box 9 Connect the blower according to the wiring diagram Figure 57 NOTE Be sure to use the wires marked Blower 10 Replace glass frame 11 Plug the AC box plug to the junction box Figure 57 12 To test blower operation Turn the fireplace on Turn blower on The blower should turn on within five 5 minutes Refer to the operating instructions on S...

Страница 42: ...one Follow the gas supplier s instruc tions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not function by hand do not try to repair it Call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under wate...

Страница 43: ...our Homeowner s Manual bag into the command center box Make sure the batteries orientation match 5 Press the master switch to the ON position Within eight 8 seconds it will beep once This indicates the system is ready 6 Press ON button Sparker will spark and pilot flame will light 7 Once pilot flame is established the main burner flame will light automatically 8 If the pilot will not stay lit afte...

Страница 44: ...liary AC Outputs Transmitter Optional RFSC RTSC RMSC Three Flame Height Settings X X X Low battery Indication for Transmitter X X X Child Proof Lock out X X X LCD Backlight X X X Security Codes X X X Thermostatic Control Mode X X Three Brightness Settings for Lights X Three Speed Control for Blower X On Off Auxiliary X Programmable Timer to turn blower on and off X BATTERY INSTALLATION The Command...

Страница 45: ...an begin Use paper clip to depress button One beep for RF receiver ON or two beeps for RF receiver OFF will be given as confirmation 2 After the RF receiver is on holding the OFF button on the Command Center while turning on the master switch will activate the learn function for the transmitter 3 After the above operation two beeps will be given and the green LED on the Command Center will flash f...

Страница 46: ...witch to the off O position 2 Press the OFF button to Medium Low then Off 3 Hold the OFF button anytime for three seconds This command of OFF will remember all last settings before turning off The next time the fireplace is turned on all settings will resume Command Center Operations The following functions are available on the Command Center Function Operation Power Up Flip the master switch to t...

Страница 47: ... frame out and lift glass frame up until it clears three tabs on top of fireplace 3 Set glass frame aside Figure 59 Removing Glass Frame Glass Frame Three Tabs Clamps Two 2 on 300 400 Units Three 3 on 500 600 Units Each clamp has a quick spring force When reinstalling clamps keep fingers clear Remove control panel to operate middle clamp on 500 and 600 units caution ...

Страница 48: ...ate Bar Center Vertical Grate Bar Log Mounting Pins rock wool placement 1 Place rock wool on burner to provide glowing embers For best results pull the rock wool apart into pieces the size of a dime or smaller NOTE Embers must be loosely placed to allow proper burner flame 2 Distribute one layer of rock wool to cover the burner Figure 60 3 Place the logs on the burner Refer to Log Placement below ...

Страница 49: ... more rock wool to the center of the burner Replace logs NOTE The type of installation vent system configuration and wind effects may cause the flame patterns to vary cleaning and maintenance Burner Pilot and Control Compartment Keep the control compartment logs and burner areas surrounding the logs clean by vacuuming or brushing at least twice a year Make sure the burner porting pilot air opening...

Страница 50: ...s may be used Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Film deposit on the inside of the glass should be cleaned off using a nontoxic non corrosive non abrasive mild cleaning solution Simply apply an adequate amount to the glass and wipe off with a damp cloth After al...

Страница 51: ...thermocouple connection at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter lead wire on the thermocouple copper lead Start the pilot and hold the valve knob in If the millivolt reading is less than 15 mV replace pilot assembly B If thermocouple is producing more than 15 mV replace ...

Страница 52: ...he pilot flame for maximum flame impingement on thermocouple A Check for flue product leak Replace defective pipe sec tion B Check horizontal venting piping is running upward 1 4 per foot Do not run the pipe level or downward C Check for proper installation and freedom from debris or blockage A Install log set per the instructions Inspect the injector and air intake area Make sure this area does n...

Страница 53: ...h Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Check valve connections Check power supply go through A E Check grounding Go through B Go through C The sensor on the pilot is not in the flame pilot flame too small ACTION Re install batteries Change batter...

Страница 54: ...54 54D0700 1 2 3 5 6 7 8 10 4 9 540700 BDV parts BDV Series Gas Fireplace illustrated parts lists firebox components ...

Страница 55: ...26D7103 10 Blower Motor 1 54D0281 26D0748 26D0748 26D0748 Accessories Field Installed Options 2 Brass Louver 1 L30BR L32BR L36BR L42BR 2 Pewter Louver 1 L30PW L32PW L36PW L42PW 5 6 7 Firebrick Walls CC 1 FB300CCW FB400CCW FB400CCW FB600CCW 8 Firebrick Floor CC 1 FB300CCF FB400CCF FB500CCF FB600CCF 5 6 7 Firebrick Walls CR 1 FB300CRW FB400CRW FB500CRW FB600CRW 8 Firebrick Floor CR 1 FB300CRF FB400C...

Страница 56: ...56 54D0700 BDV Series Gas Fireplace illustrated parts lists Standing Pilot Millivolt control 1 2C 2I 2T 2 4 5 6 3 8 9 7 10 11 12 13 14 540700 BDV control parts ...

Страница 57: ...D0048 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 7 Injector 1 62D3006 20H3146 62D3004 20H3143 20H3145 57D0210 20H3145 57D0210 8 Burner Assembly 1 54D0200 54D0200 54D0001 54D0001 54D0329 54D0329 54D0329 54D0329 9 Venturi 1 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 10 Wire Assembly 1 44D0500 44D0500 44D0500 ...

Страница 58: ...58 54D0700 BDV Series Gas Fireplace illustrated parts lists ELECTRONIC IGNITION 1 2 4 5 6 3 8 9 7 10 11 540700 BDV electronic parts L O HI 24V 6 24V GND 5 PV 3 MV PV 2 MV 1 GND BURNER 4 SENSE 8 SPARK 9 ...

Страница 59: ...ff Valve 1 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 23D6046 5 Rocker Switch 1 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 6 Injector 1 62D3006 20H3146 62D3004 20H3143 20H3145 57D0210 20H3145 57D0210 7 Burner Assembly 1 54D0200 54D0200 54D0001 54D0001 54D0329 54D0329 54D0329 54D0329 8 Venturi 1 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 9 Wire...

Страница 60: ...60 54D0700 BDV Series Gas Fireplace illustrated parts lists SIGNATURE COMMAND SYSTEM 0009 SG parts 8 08 1 2 3 4 17 5 6 7 8 9 13 14 15 ...

Страница 61: ...0329 54D0329 54D0329 54D0329 9 Venturi 1 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 45D0600 10 Wire Valve Control not shown 1 80D0010 80D0010 80D0010 80D0010 80D0010 80D0010 80D0010 80D0010 11 Wire Command Ctr Control Box 2 1 80D0008 80D0008 80D0008 80D0008 80D0008 80D0008 80D0008 80D0008 not shown Accessories 13 Hand Held Remote Control w HI LO Timer 1 RMSC RMSC RMSC RMSC 14 Hand Hel...

Страница 62: ...62 54D0700 BDV Series Gas Fireplace Vent Components illustrated parts list HOT 1 2 3 4 5 6 9 7 8 11 10 0004 MLDV vent parts ...

Страница 63: ...cal Termination Cap 46DVA VC 980 4DT VC 3 6 6 Pipe Length galvanized 46DVA 06 908 4DT 06 3 6 9 Pipe Length galvanized 46DVA 09 907 4DT 09 3 6 12 Pipe Length galvanized 46DVA 12 906 4DT 1 3 6 24 Pipe Length galvanized 46DVA 24 904 4DT 4 3 6 36 Pipe Length galvanized 46DVA 36 903 4DT 36 3 6 48 Pipe Length galvanized 46DVA 48 902 4DT 48 4 6 81 2 Pipe Extension galvanized 46DVA 08A 4DT AJ 4 6 16 Pipe ...

Страница 64: ...ogs illustrated parts lists Item Description Qty BDV300 BDV400 BDV500 BDV600 1 Rear Log 1 54D0121 54D0181 54D0339 54D0339 2 Right Log 1 54D0147 54D0116 54D0361 54D0361 3 Left Log 1 54D0146 54D0115 54D0360 54D0360 1 3 2 540700 BDV log parts ...

Страница 65: ... than seven 7 feet above finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall hori zontal vented gas fueled equipment the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and ...

Страница 66: ...ntial purposes c MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manu facturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instructions provided by the manufacturer for installation of the equipment and the venting system shall include 1 Detailed instructions for the in...

Страница 67: ...ll also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly damage by accident neglect misuse abuse alterations negligence of others including the installation thereof by unqualified installers 2 the costs of removal reinstallation or transportation of defec tive parts on the ap...

Страница 68: ...40361 www mhsc com Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency BDV300NV 57 9 BDV300PV 53 8 BDV300NE 61 8 BDV300PE 55 7 BDV400NV 58 4 BDV400PV 58 5 BDV400NE 61 1 BDV400PE 60 7 BDV500NV 58 7 BDV500PV 58 8 BDV500NE 61 3 BDV500PE 60 8 BDV600NV 58 4 BDV600PV 58 5 BDV600NE 60 9 BDV600PE 60 5 ...

Отзывы: