![Mitsubishi MR-JE-100A Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/mitsubishi/mr-je-100a/mr-je-100a_instruction-manual_1808430048.webp)
2. SIGNALS AND WIRING
2 - 27
2.6 Power-on sequence
POINT
The voltage of analog monitor output, output signal, etc. may be unstable at
power-on.
(1) Power-on procedure
1) Always use a magnetic contactor for the power supply wiring (L1/L2/L3) as shown in section 3.1
of "MR-JE-_A Servo Amplifier Instruction Manual". Configure an external sequence to switch off
the magnetic contactor as soon as an alarm occurs.
2) The servo amplifier receives the SON (Servo-on) in 4 s to 5 s after the power supply is switched
on. Therefore, when SON (Servo-on) is switched on simultaneously with the power supply, the
base circuit will switch on in about 4 s to 5 s, and the RD (Ready) will switch on in further about 5
ms, making the servo amplifier ready to operate. (Refer to (2) in this section.)
3) When RES (Reset) is switched on, the base circuit is shut off and the servo motor shaft coasts.
(2) Timing chart
95 ms
95 ms
RD (Ready)
RES (Reset)
SON (Servo-on)
OFF
ON
OFF
ON
ON
OFF
Base circuit
OFF
ON
Power supply
OFF
ON
10 ms
5 ms
10 ms
10 ms
5 ms
10 ms
5 ms
10 ms
(4 s to 5 s)
SON (Servo-on) accepted
Alarming (OFF)
No alarming (ON)
ALM (Malfunction)
4 s to 5 s
Содержание MR-JE-100A
Страница 49: ...2 SIGNALS AND WIRING 2 28 MEMO...
Страница 73: ...3 DISPLAY AND OPERATION SECTIONS 3 24 MEMO...
Страница 213: ...5 HOW TO USE THE PROGRAM 5 68 MEMO...
Страница 275: ...6 APPLICATION OF FUNCTIONS 6 62 MEMO...
Страница 355: ...8 TROUBLESHOOTING 8 8 MEMO...
Страница 359: ...9 OPTIONS AND PERIPHERAL EQUIPMENT 9 4 MEMO...
Страница 391: ...10 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 10 32 MEMO...