7. PARAMETERS
7 - 47
7.2.4 I/O setting parameters ([Pr. PD_ _ ])
No./symbol/
name
Setting
digit
Function
Initial
value
[unit]
Control
mode
CP CL
PD01
*DIA1
Input signal
automatic on
selection 1
Select input devices to turn on automatically.
_ _ _ x
(HEX)
_ _ _ x (BIN): For manufacturer setting
0h
_ _ x _ (BIN): For manufacturer setting
_ x _ _ (BIN): SON (Servo-on)
0: Disabled (Use for an external input signal.)
1: Enabled (automatic on)
x _ _ _ (BIN): For manufacturer setting
_ _ x _
(HEX)
_ _ _ x (BIN): PC (Proportional control)
0h
0: Disabled (Use for an external input signal.)
1: Enabled (automatic on)
_ _ x _ (BIN): TL (External torque limit selection)
0: Disabled (Use for an external input signal.)
1: Enabled (automatic on)
_ x _ _ (BIN): For manufacturer setting
x _ _ _ (BIN): For manufacturer setting
_ x _ _
(HEX)
_ _ _ x (BIN): For manufacturer setting
0h
_ _ x _ (BIN): For manufacturer setting
_ x _ _ (BIN): LSP (Forward rotation stroke end)
0: Disabled (Use for an external input signal.)
1: Enabled (automatic on)
x _ _ _ (BIN): LSN (Reverse rotation stroke end)
0: Disabled (Use for an external input signal.)
1: Enabled (automatic on)
x _ _ _
(HEX)
_ _ _ X (BIN): EM2 (Forced stop 2)
0: Disabled (Use for an external input signal.)
1: Enabled (automatic on)
0h
_ _ x _ (BIN): For manufacturer setting
_ x _ _ (BIN): For manufacturer setting
x _ _ _ (BIN): For manufacturer setting
Содержание MR-JE-100A
Страница 49: ...2 SIGNALS AND WIRING 2 28 MEMO...
Страница 73: ...3 DISPLAY AND OPERATION SECTIONS 3 24 MEMO...
Страница 213: ...5 HOW TO USE THE PROGRAM 5 68 MEMO...
Страница 275: ...6 APPLICATION OF FUNCTIONS 6 62 MEMO...
Страница 355: ...8 TROUBLESHOOTING 8 8 MEMO...
Страница 359: ...9 OPTIONS AND PERIPHERAL EQUIPMENT 9 4 MEMO...
Страница 391: ...10 COMMUNICATION FUNCTION MITSUBISHI ELECTRIC GENERAL PURPOSE AC SERVO PROTOCOL 10 32 MEMO...