11 - 197 11 - 197
MELSEC-Q
11 INSTRUCTIONS AND FUNCTIONS
Program Example
(1) Program example for a format 1 control table
100 ' A program example that loads the microcomputer program and saves it on a memory card
110 ' (Capacity of the microcomputer program: 8 k bytes)
120 OPEN"0:PROG9.DAT"FOR OUTPUT AS #1
:
'Opens the sequential file
130 DIM TBL%(4),A%(127)
:
'Defines arrays
140 TBL%(0)=255
:
'Specifies the station number to
communicate with to the local station
150 TBL%(1)=9
:
'Specifies to load the microcomputer
program
160 TBL%(2)=1
:
'Specifies to load the main microcomputer
program
170 TBL%(4)=128
:
'Specifies the number of bytes to be read
180 FOR J=&HO TO &H1F80 STEP 128
190 TBL%(3)=J
:
'Specifies the starting address of the
program
200 PCRD TBL%( ),A%( )
:
'Executes the load operation
210 FOR I=0 TO 127
220 PRINT #1,A%(I)
:
'Writes to the sequential file
230 NEXT I
240 NEXT J
250 CLOSE #1
:
'Closes the file
260 END
Содержание A1SD51S
Страница 183: ...11 13 11 13 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS RUN Before swap A 0 H924 A 1 H1159 After swap A 0 H1159 A 1 H924 OK...
Страница 331: ...11 161 11 161 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CON ON OFF STOP and ZOPEN functions and Section 7 4...
Страница 557: ...11 387 11 387 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CHR SPACE and SPC functions...
Страница 629: ...11 459 11 459 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZOPEN ZSEND and ZCNTL instructions and Section 7 3 4...
Страница 645: ...11 475 11 475 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZEVENT ZSIGNAL and DEF ZEVENT instructions...