11 - 326 11 - 326
MELSEC-Q
11 INSTRUCTIONS AND FUNCTIONS
(2) Program example for a format 2 control table
100 'A program example that writes data to a Q/QnA series PLC CPU’s device memory
110 DIM TBL%(10),A%(20)
:
'Defines arrays
120 TBL%(0)=256
:
'Specifies a format 2 control table
130 TBL%(1)=1
:
'Specifies network number 1
140 TBL%(2)=1
:
'Specifies station number 1
150 TBL%(4)=515
:
'Specifies to write data to device memory of
the Q/QnA series CPU
160 TBL%(5)=144
:
'Specifies internal relays M
170 D!=0
180 H!=INT(D!/65536!)
:
'Splits into lower and higher digits
190 L!=D!-H!*65536!
200 H$=RIGHT$(“0000”+HEX$(H!),4)
210 L$=RIGHT$(“0000”+HEX$(L!),4)
220 TBL%(6)=VAL(“&H”+L$)
:
'Specifies the starting number (lower) of the
device to be written
230 TBL%(7)=VAL(“&H”+H$)
:
'Specifies the starting number (higher) of
the device to be written
240 TBL%(8)=16
:
'Specifies the number of points to be
written
250 A%(0)=&HF
260 PCWT TBL%( ),A%( )
:
'Executes the write operation
270 END
(3) Program example a for format 3 control table
100 'A program example that writes data to a Q/QnA series PLC CPU’s device memory
110 DIM TBL%(10),A%(20)
:
'Defines arrays
120 TBL%(0)=256
:
'Specifies a format 3 control table
130 TBL%(1)=1
:
'Specifies network number 1
140 TBL%(2)=1
:
'Specifies station number 1
150 TBL%(4)=515
:
'Specifies to write data to device memory of
the Q/QnA series CPU
160 TBL%(5)=&H3E3
:
'Specifies the requested CPU (PLC No.4)
170 TBL%(6)=144
:
'Specifies internal relays M
180 D!=0
190 H!=INT(D!/65536!)
:
’Splits into lower and higher digits
200 L!=D!-H!*65536!
210 H$=RIGHT$(“0000”+HEX$(H!),4)
220 L$=RIGHT$(“0000”+HEX$(L!),4)
230 TBL%(7)=VAL(“&H”+L$)
:
'Specifies the starting number (lower) of the
device to be written
240 TBL%(8)=VAL(“&H”+H$)
:
'Specifies the starting number (higher) of
the device to be written
250 TBL%(9)=16
:
'Specifies the number of points to be
written
260 A%(0)=&HF
270 PCWT TBL%( ),A%( )
:
'Executes the write operation
280 END
Содержание A1SD51S
Страница 183: ...11 13 11 13 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS RUN Before swap A 0 H924 A 1 H1159 After swap A 0 H1159 A 1 H924 OK...
Страница 331: ...11 161 11 161 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CON ON OFF STOP and ZOPEN functions and Section 7 4...
Страница 557: ...11 387 11 387 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CHR SPACE and SPC functions...
Страница 629: ...11 459 11 459 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZOPEN ZSEND and ZCNTL instructions and Section 7 3 4...
Страница 645: ...11 475 11 475 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZEVENT ZSIGNAL and DEF ZEVENT instructions...