4 - 3 4 - 3
MELSEC-Q
4 THE EXCHANGE BETWEEN THE PLC AND BUFFER MEMORY
4.2.2 PLC station number
In AD51H-BASIC, not only can the PLC attached to the communication module be
accessed, but PLCs of other stations that are data-linked via the MELSECNET can be
accessed as well. However, the following restrictions apply depending on whether the
PLC with the communication module attached is a master station (control station) or
local station (standard station).
(1) MELSECNET (II), MELSECNET/B
(a) When the CPU with the communication module attached (self station) is a
MELSEC two-tier master station, data from all local stations and remote I/O
stations within the self station and two-tier loop can be accessed.
Only the buffer memory of the special function module can be accessed for
remote I/O stations.
Local Station #1
(self station)
(Master
Station)
Communication
module
(Local Station #1)
(Local Station #2)
Remote Station #2
Local Station #3
Master Station
The names in
parentheses are
station names
under a three-tier
system.
(b) When the CPU with the communication module attached (self station) is a
MELSEC two-tier or three-tier local station, only the data from the self
station and master stations within the same loop can be accessed.
Local Station #1
Self
station
(Master
Station)
Communication
Module
(Local Station #1)
(Local Station #2)
Remote Station #2
Master Station
Local Station #1
self station
(Master
Station)
(Local Station #2)
Remote Station #2
Local Station #3
Master Station
Local Station #3
Communication Module
Local Station #1
The names in
parentheses are
station names
under a three-tier
system.
The names in
parentheses are
station names
under a three-tier
system.
Содержание A1SD51S
Страница 183: ...11 13 11 13 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS RUN Before swap A 0 H924 A 1 H1159 After swap A 0 H1159 A 1 H924 OK...
Страница 331: ...11 161 11 161 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CON ON OFF STOP and ZOPEN functions and Section 7 4...
Страница 557: ...11 387 11 387 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CHR SPACE and SPC functions...
Страница 629: ...11 459 11 459 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZOPEN ZSEND and ZCNTL instructions and Section 7 3 4...
Страница 645: ...11 475 11 475 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZEVENT ZSIGNAL and DEF ZEVENT instructions...