11 - 259 11 - 259
MELSEC-Q
11 INSTRUCTIONS AND FUNCTIONS
• When word units are specified
• Bit devices
• Word devices
1 to 32 words
1 to 64 points
Format 2 control table
%(0)
• • • • • •
Format 2 control table
• Specify 256.
%(1)
• • • • • •
Specify the number of the network to be accessed.
See Section 4.2.2 for the allowable specification range.
%(2)
• • • • • •
Specify the station number of the PLC CPU to which data is
written.
See Section 4.2.2 for the allowable specification range.
%(3)
• • • • • •
Detailed error codes are stored here.
See Appendix 4.4.2 for the details about the error codes.
%(4)
• • • • • •
Processing code
• Specify 1.
%(5)
• • • • • •
Specify the device processing unit.
• When reading in bit units • • • • • 1
• When reading in word units • • • 2
%(6)
• • • • • •
Specify the device using the defined code.
See Section 4.2.5 for the code numbers.
%(7)
• • • • • •
Specify the device number of the device specified in %(4).
See Section 4.2.5 for the allowable specification range.
Note, however, that values other than 0 or multiples of 16
cannot be specified for device numbers when writing to bit
devices in word units.
%(8)
• • • • • •
Specify the number of device points to be written, including
the device specified in %(6) and %(7).
The allowable specification range is as follows:
• When bit units are specified
• Bit devices
1 to 256 points
• When word units are specified
• Bit devices
• Word devices
1 to 32 words
1 to 64 points
Содержание A1SD51S
Страница 183: ...11 13 11 13 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS RUN Before swap A 0 H924 A 1 H1159 After swap A 0 H1159 A 1 H924 OK...
Страница 331: ...11 161 11 161 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CON ON OFF STOP and ZOPEN functions and Section 7 4...
Страница 557: ...11 387 11 387 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CHR SPACE and SPC functions...
Страница 629: ...11 459 11 459 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZOPEN ZSEND and ZCNTL instructions and Section 7 3 4...
Страница 645: ...11 475 11 475 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZEVENT ZSIGNAL and DEF ZEVENT instructions...