11 - 328 11 - 328
MELSEC-Q
11 INSTRUCTIONS AND FUNCTIONS
Format 1 control table
%(0)
• • • • • •
Specify the station number of the PLC CPU to which data is
written.
See Section 4.2.2 for the allowable specification range.
%(1)
• • • • • •
Processing code
• Specify 516 (&H204).
%(2)
• • • • • •
Specify the number of points for word devices (lower) and
bit devices (higher) to be written.
1
%(3)
• • • • • •
Specify the number of double-word device points to be
written.
1
%(4)
• • • • • •
Specify the device type using the defined code.
• See Section 4.2.5 for the code numbers.
%(5)
• • • • • •
Specify the device number (lower) of the specified device.
See Section 4.2.5 for the allowable specification range.
%(6)
• • • • • •
Specify the device number (higher) of the specified device.
See Section 4.2.5 for the allowable specification range.
%(7)
• • • • • •
Specify the device processing unit.
• When writing in bit units
• When writing to word devices
in word/double-word units
• When writing to bit devices in
word units
• When writing to bit devices in
double-word units
• • • 0 (&H0)
• • • 0 (&H0)
• • • 8960 (&H2300)
• • • 9984 (&H2700)
%(8)
• • • • • •
Fixed value
• Specify 0 (&H0).
1: The number of points to be written should be within the following ranges:
• In case of a Q series CPU
1
≤
(number of bit device points 12 + number of word device points 12
+ number of double-word device points
14)
≤
1920 points
• In case of a QnA series CPU
1
≤
(number of bit device points 12+ number of word device points 12
+ number of double-word device points
14)
≤
960 points
Содержание A1SD51S
Страница 183: ...11 13 11 13 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS RUN Before swap A 0 H924 A 1 H1159 After swap A 0 H1159 A 1 H924 OK...
Страница 331: ...11 161 11 161 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CON ON OFF STOP and ZOPEN functions and Section 7 4...
Страница 557: ...11 387 11 387 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CHR SPACE and SPC functions...
Страница 629: ...11 459 11 459 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZOPEN ZSEND and ZCNTL instructions and Section 7 3 4...
Страница 645: ...11 475 11 475 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZEVENT ZSIGNAL and DEF ZEVENT instructions...