4 - 12 4 - 12
MELSEC-Q
4 THE EXCHANGE BETWEEN THE PLC AND BUFFER MEMORY
4.2.3 Choosing a process
Process requests of PCRD and PCWT instructions are specified using values referred
to as process codes. For details, see the descriptions of the PCRD and PCWT
instructions.
4.2.4 Bit/Word designation
Bit/Word designation refers to the designation of processing in 1-bit units or 1-word
(16-bit) units when the PLC accesses the bit device.
Only one point
is accessed
Bit
designation
16 points are
accessed
as a group
Word
designation
M0
to
M0
to
M15
M8 M7
When word-unit process is specified, 16 bits of process points will be specified. Also,
when word-unit is specified, the starting number of the respective device must be
specified as 0 or a multiple of 16.
Example
For M,
M0, M16, M32,
• • • •
are used as starting numbers.
For B,
B0, B10, B20,
• • • •
are used as starting numbers.
When processing special relay M in word units, the starting number may be 9000
or a multiple of 16 added to 9000.
(M9000,
M9016,
M9032,
can be used as starting numbers.)
…………
When accessing word devices, use word unit processing.
REMARK
Access • • • I/O processing such as data read and write.
Содержание A1SD51S
Страница 183: ...11 13 11 13 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS RUN Before swap A 0 H924 A 1 H1159 After swap A 0 H1159 A 1 H924 OK...
Страница 331: ...11 161 11 161 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CON ON OFF STOP and ZOPEN functions and Section 7 4...
Страница 557: ...11 387 11 387 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CHR SPACE and SPC functions...
Страница 629: ...11 459 11 459 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZOPEN ZSEND and ZCNTL instructions and Section 7 3 4...
Страница 645: ...11 475 11 475 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZEVENT ZSIGNAL and DEF ZEVENT instructions...