11 - 226 11 - 226
MELSEC-Q
11 INSTRUCTIONS AND FUNCTIONS
Format 3 control table
%(0)
• • • • • •
Format 3 control table
• Specify 257 (&H101).
%(1)
• • • • • •
Specify the network number of the network to be accessed.
See Section 4.2.2 for the allowable specification range.
%(2)
• • • • • •
Specify the station number of the PLC CPU whose type
name is to be read.
See Section 4.2.2 for the allowable specification range.
%(3)
• • • • • •
Detailed error codes are stored here.
See Appendix 4.4.2 for the details about the error codes.
%(4)
• • • • • •
Specify the requested CPU.
• PLC No.1
• PLC No.2
• PLC No.3
• PLC No.4
• Control PLC
• • • • • •
• • • • • •
• • • • • •
• • • • • •
• • • • • •
992 (&H3E0)
993 (&H3E1)
994 (&H3E2)
995 (&H3E3)
1023 (&H3FF)
%(5)
• • • • • •
Processing code
• Specify 513 (&H201).
%(6)
• • • • • •
Fixed value
• Specify 0 (&H0).
• The type name of the Q series CPU is stored using the following codes in <storage
area for data read>.
CPU type name
Type name string
Type name code
Q2ACPU
Q2ACPU
&H0021
Q2ACPU-S1
Q2ACPU-S1
&H0022
Q3ACPU
Q3ACPU
&H0023
Q4ACPU
Q4ACPU
&H0024
Q02CPU
Q02CPU
&H0041
Q02HCPU
Q02HCPU
&H0041
Q06HCPU
Q06HCPU
&H0042
Q12HCPU
Q12HCPU
&H0043
Q25HCPU
Q25HCPU
&H0044
% (0) to % (7)
Type name string
The type name string is stored
here.
% (8)
Type name code
The type name code is stored
here.
% (9) to % (31)
Dummy
Dummy bytes (0) are stored here.
Содержание A1SD51S
Страница 183: ...11 13 11 13 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS RUN Before swap A 0 H924 A 1 H1159 After swap A 0 H1159 A 1 H924 OK...
Страница 331: ...11 161 11 161 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CON ON OFF STOP and ZOPEN functions and Section 7 4...
Страница 557: ...11 387 11 387 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the CHR SPACE and SPC functions...
Страница 629: ...11 459 11 459 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZOPEN ZSEND and ZCNTL instructions and Section 7 3 4...
Страница 645: ...11 475 11 475 MELSEC Q 11 INSTRUCTIONS AND FUNCTIONS REMARK See the ZEVENT ZSIGNAL and DEF ZEVENT instructions...