5 POSITIONING CONTROL
5.17 Continuous Trajectory Control
341
5
Specification of pass points by repetition instructions
This section describes the method of the pass points for which executes between any pass points repeatedly.
: Must be set,
: Set if required
*1 Only when the reference axis speed is specified
Processing details
The first of repetition range is set by the following instructions.
■
FOR-TIMES (number of loops setting)
• The repetition range set specified number of times is executed repeatedly.
• The setting range is 1 to 32767. Outside the range of -32768 to 0 is controlled as a setting of "1".
• A decimal constant (K), a hexadecimal constant (H), or a word device can be used for the number of repetition times. Refer
to the following for the setting range of usable devices.
MELSEC iQ-R Motion controller Programming Manual (Common)
■
FOR-ON (Loop-out trigger condition setting)
• The repetition range set until the specified bit device turns on is executed repeatedly.
• A bit device (or a specified bit in a word device) can be used for the loop-out trigger condition. Refer to the following for the
setting range of usable devices.
MELSEC iQ-R Motion controller Programming Manual (Common)
■
FOR-OFF (loop-out trigger condition setting)
• The repetition range set until the specified bit device turns off is executed repeatedly.
• A bit device (or a specified bit in a word device) can be used for the loop-out trigger condition. Refer to the following for the
setting range of usable devices.
MELSEC iQ-R Motion controller Programming Manual (Common)
Positioning data set in servo instructions
Common
Servo
instruction
Positioning
method
Number
of
control
axes
Arc
OSC
Parameter block
Others
Parameter block No.
Acceleration time
Deceleration time
Rapid Stop deceleration time
Torque limit value
Deceleration processing on stop input
Allowable error range for circular interpolation
S-curve ratio
Advanced S-curve acceleration/deceleration
Bias speed at start
Repeat condition
Program No.
Command speed (Continuous trajectory)
Skip
FIN acceleration/deceleration
WAIT-ON/OFF
Fixed position stop
Axis
Address/travel value
Command speed
Dwell time
M-code
Torque limit value
Auxiliary point
Radius
Central point
Number of pitches
Starting angle
Amplitude
Frequency
Interpolation control unit
Speed limit value
Reference axis No.
*1
Fixed position stop acceleration/deceleration time
FOR-TIMES
FOR-ON
FOR-OFF
NEXT
Содержание MELSEC iQ-R16MTCPU
Страница 1: ...MELSEC iQ R Motion Controller Programming Manual Positioning Control R16MTCPU R32MTCPU R64MTCPU ...
Страница 2: ......
Страница 477: ...APPENDICES Appendix 1 Processing Times of the Motion CPU 475 A MEMO ...
Страница 481: ......