M70V Series Connection Manual
4.4 Connection of Remote I/O Unit
133
4.4.2 Station No. Setting when Using Multiple Remote I/O Units
Multiple remote I/O units can be used, as long as the total No. of occupied stations connected with serial links is
eight or less. (three/four or less when connected to the operation panel I/O unit).
When using multiple remote I/O units, a characteristic station No. must be set for each unit. The FCUA-DX10x unit
has one rotary switch, FCUA-DX11x, DX12x and DX14x unit have two. Each of these switches must be set to a
characteristic station No. within a range of 0 to 7 (2 or 3 to 5 when connected to the operation panel I/O unit).
When connecting directly to the control unit
Setting example 1
Total number of occupied stations: 1
Setting example 2
Number of occupied stations: 1 2
Total number of occupied stations: 3
Unit type
Number of occupied stations
FCUA-DX10x
1
FCUA-DX11x
2
FCUA-DX12x
2
FCUA-DX14x
2
0
+
FCUA-DX100/101
0
1
2
+
+
FCUA-DX100/101
FCUA-DX110/111
or
FCUA-DX120/121
Содержание M70V Series
Страница 1: ......
Страница 13: ......
Страница 15: ......
Страница 17: ......
Страница 19: ......
Страница 21: ......
Страница 25: ......
Страница 26: ...1 1 System Configuration ...
Страница 36: ...11 2 General Specifications ...
Страница 110: ...85 3 Installation ...
Страница 120: ...95 4 Connection ...
Страница 173: ...4 Connection MITSUBISHI CNC 148 ...
Страница 174: ...149 付録 Ap 1 章 149 Appendix 1 Cable ...
Страница 220: ...195 付録 Ap 2 章 195 Appendix 2 EMC Installation Guidelines ...
Страница 232: ...207 付録 Ap 3 章 207 Appendix 3 Restrictions for Lithium Batteries ...
Страница 241: ...Appendix 3 Restrictions for Lithium Batteries MITSUBISHI CNC 216 ...
Страница 242: ...217 付録 Ap 4 章 217 Appendix 4 Precautions for Compliance to UL c UL Standards ...
Страница 246: ......
Страница 250: ......