Check first when you have a trouble
5.5.9
Operation mode is not changed properly
5.5.10 Operation panel display is not operating
5.5.11 Motor current is too large
Check
points
Possible Cause
Countermeasures
Refer
to
page
Input
signal
Start signal (STF or STR) is ON.
Check that the STF and STR signals are OFF.
When either is ON, the operation mode cannot be
changed.
Parameter
Setting
Pr. 79
setting is improper.
When
Pr. 79 Operation mode selection
setting is "0" (initial
value), the inverter is placed in the External operation mode
at input power ON. To switch to the PU operation mode,
press
on the operation panel (press
when the
parameter unit (FR-PU04/FR-PU07) is used). At other
settings (1 to 4, 6, 7), the operation mode is limited
accordingly.
Operation mode and a writing device do not
correspond.
Check
Pr. 79, Pr. 338, Pr. 339, Pr. 551,
and select an
operation mode suitable for the purpose.
Check
points
Possible Cause
Countermeasures
Refer
to
page
Main
Circuit
Wiring or installation is improper.
Check for the wiring and the installation.
Make sure that the connector is fitted securely across
terminal P/+ to P1.
Main
Circuit
Control
Circuit
Power is not input.
Input the power.
Parameter
Setting
Command sources at the PU operation mode is not at
the operation panel.
(None of the operation mode displays (
)
is lit.)
Check the setting of
Pr. 551 PU mode operation command
source selection.
(If parameter unit (FR-PU04/FR-PU07) is connected
while
Pr. 551
= "9999" (initial setting), all the operation
mode displays (
) turn OFF.)
Check
points
Possible Cause
Countermeasures
Refer
to
page
Parameter
Setting
Torque boost
(Pr. 0, Pr. 46)
setting is improper under V/F
control, so the stall prevention function is activated.
Increase/decrease
Pr. 0 Torque boost
setting value by
0.5% increments to the setting.
V/F pattern is improper when V/F control is performed.
(
Pr. 3, Pr. 14, Pr. 19
)
Set rated frequency of the motor to
Pr. 3 Base frequency
.
Use
Pr. 19 Base frequency voltage
to set the base voltage
(e.g. rated motor voltage).
Change
Pr. 14 Load pattern selection
according to the load
characteristic.
Stall prevention function is activated due to a heavy
load.
Reduce the load weight.
—
Set
Pr. 22 Stall prevention operation level
higher according
to the load. (Setting
Pr. 22
too large may result in
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor.
—
Auto tuning is not performed under General-purpose
magnetic flux vector control.
Perform offline auto tuning.
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...