277
Inspection items
6.1.5
Checking the inverter and converter modules
<Preparation>
(1) Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W).
(2) Prepare a tester. (Use 100
Ω
range.)
<Checking method>
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W,
P/
+ and
N/
-, and check for
continuity.
<Module device numbers and terminals to be checked>
z
Three-phase 200V class, Three-phase 400V class, single-phase 200V class
z
Single-phase 100V class
NOTE
1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of discontinuity, the measured value is almost
∞
. When there is an instantaneous continuity, due to the
smoothing capacitor, the tester may not indicate
∞
.
At the time of continuity, the measured value is several to
several tens-of ohms depending on the module type, circuit tester type, etc. If all measured values are almost the
same, the modules are without fault.
Tester Polarity
Measured
Value
Tester Polarity
Measured
Value
Conver
te
r
mod
ul
e
D1
R/L1
P/+
Discontinuity
D4
R/L1
N/-
Continuity
P/+
R/L1 Continuity
N/-
R/L1 Discontinuity
D2
S/L2
P/+
Discontinuity
D5
S/L2
N/-
Continuity
P/+
S/L2 Continuity
N/-
S/L2 Discontinuity
D3
∗
T/L3
∗
P/+
Discontinuity
D6
∗
T/L3
∗
N/-
Continuity
P/+
T/L3
∗
Continuity
N/-
T/L3
∗
Discontinuity
In
vert
er
mod
u
le
TR1
U
P/+
Discontinuity
TR4
U
N/-
Continuity
P/+
U
Continuity
N/-
U
Discontinuity
TR3
V
P/+
Discontinuity
TR6
V
N/-
Continuity
P/+
V
Continuity
N/-
V
Discontinuity
TR5
W
P/+
Discontinuity
TR2
W
N/-
Continuity
P/+
W
Continuity
N/-
W
Discontinuity
(Assumes the use of an analog meter.)
* T/L3, D3 and D6 are only for the three-phase power input specification models.
Tester Polarity
Measured
Value
Tester Polarity
Measured
Value
Conver
ter
module
D1
S/L2
P/+
Discontinuity
—
R/L1
P/+
Discontinuity
P/+
S/L2 Continuity
P/+
R/L1 Discontinuity
D2
S/L2
N/-
Continuity
R/L1
N/-
Discontinuity
N/-
S/L2 Discontinuity
N/-
R/L1 Discontinuity
In
ve
rte
r
m
odule
TR1
U
P/+
Discontinuity
TR4
U
N/-
Continuity
P/+
U
Continuity
N/-
U
Discontinuity
TR3
V
P/+
Discontinuity
TR6
V
N/-
Continuity
P/+
V
Continuity
N/-
V
Discontinuity
TR5
W
P/+
Discontinuity
TR2
W
N/-
Continuity
P/+
W
Continuity
N/-
W
Discontinuity
(Assumes the use of an analog meter.)
Converter module
Inverter module
D1
D2
D3
D4
D5
D6
TR1
TR3
TR5
TR4
TR6
TR2
U
V
W
R/L1
S/L2
T/L3
C
P/+
N/-
Converter module
Inverter module
D1
D2
TR1
TR3
TR5
TR4
TR6
TR2
U
V
W
R/L1
S/L2
C
C
P/+
N/-
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...