289
Rating
Single-phase 200V power supply
Single-phase 100V power supply
∗1
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
∗2
The rated output capacity indicated assumes that the output voltage is 230V.
∗3
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function
(Pr. 57)
or
power failure stop function
(Pr. 261)
is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection
level and load of 100% or more may not be available.
∗4
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about
that of the power supply.
∗5
The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large.
(Option brake resistor cannot be used for 0.1K and 0.2K.) A brake unit (FR-BU2) may also be used.
∗6
The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
∗7
For single-phase 100V power input model, the maximum output voltage is twice the amount of the power supply voltage and cannot be exceeded.
∗8
In a single-phase 100V power input model, the output voltage may fall down when the load is heavy, and larger output current may flow compared to a three-
phase input model. Use the motor with less load so that the output current is within the rated motor current range.
Model FR-D720S- K
0.1
0.2
0.4
0.75
1.5
2.2
Applicable motor capacity (kW)
0.1
0.2
0.4
0.75
1.5
2.2
Ou
tp
u
t
Rated capacity (kVA)
0.3
0.6
1.0
1.7
2.8
4.0
Rated current (A)
0.8
1.4
2.5
4.2
7.0
10.0
Overload current rating
150% 60s, 200% 0.5s (inverse-time characteristics)
Rated voltage
Three-phase 200 to 240V
Regenerative braking torque
150%
100%
50%
20%
Pow
e
r supp
ly
Rated input AC voltage/frequency
Single-phase 200 to 240V 50Hz/60Hz
Permissible AC voltage fluctuation
170 to 264V 50Hz/60Hz
Permissible frequency fluctuation
±5%
Power supply capacity (kVA)
0.5
0.9
1.5
2.3
4.0
5.2
Protective structure (JEM1030)
Enclosed type (IP20)
Cooling system
Self-cooling
Forced air cooling
Approximate mass (kg)
0.5
0.5
0.9
1.1
1.5
2.0
Model FR-D710W- K
0.1
0.2
0.4
0.75
Applicable motor capacity (kW)
0.1
0.2
0.4
0.75
Ou
tp
u
t
Rated capacity (kVA)
0.3
0.6
1.0
1.7
Rated current (A)
0.8
1.4
2.5
4.2
Overload current rating
150% 60s, 200% 0.5s
(inverse-time characteristics)
Rated voltage
Three-phase 200 to 230V
Regenerative braking torque
150%
100%
P
o
wer s
upply
Rated input AC voltage/frequency
Single-phase 100 to 115V 50Hz/60Hz
Permissible AC voltage fluctuation
90 to 132V 50Hz/60Hz
Permissible frequency fluctuation
±5%
Power supply capacity (kVA)
0.5
0.9
1.5
2.5
Protective structure (JEM1030)
Enclosed type (IP20)
Cooling system
Self-cooling
Approximate mass (kg)
0.6
0.7
0.9
1.4
2
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...