Operation selection at power failure and instantaneous power failure
When
Pr. 162
= 1, 11 (without frequency search)
(1) Automatic restart operation selection
(Pr. 30, Pr. 162, Pr. 299)
Without frequency search
When
Pr. 162
= "1 (initial value) or 11", automatic restart
operation is performed in a reduced voltage system,
where the voltage is gradually risen with the output
frequency unchanged from prior to an instantaneous
power failure independently of the coasting speed of the
motor.
When
Pr. 162
= 0, 10 (with frequency search)
With frequency search
When "0 or 10" is set in
Pr. 162
, the inverter smoothly starts
after detecting the motor speed upon power restoration.
(The motor capacity should be equal to or one rank lower
than the inverter capacity)
When using the frequency search, perform offline auto
tuning.
(Refer to page
for General-purpose magnetic flux
vector control and
page
for V/F control.)
During reverse rotation, the inverter can be restarted
smoothly as the direction of rotation is detected.
You can select whether to make rotation direction
detection or not with
Pr. 299 Rotation direction detection
selection at restarting
.
When capacities of the motor and inverter differ, set "0"
(without rotation direction detection) in
Pr. 299
.
REMARKS
Speed detection time (frequency search) changes according to the motor speed. (maximum 150ms)
When the inverter capacity is two rank or more larger than the motor capacity, the inverter may not start due to overcurrent trip (E.OC ).
If two or more motors are connected to one inverter, the function does not operate properly. (The inverter does not start
smoothly.)
When reverse rotation is detected under the condition of
Pr. 78
= "1" (reverse rotation disabled), the rotation direction is
changed to forward rotation after decelerates in reverse rotation when the start command is forward rotation. The inverter will
not start when the start command is reverse rotation.
Instantaneous (power failure) time
Coasting time
Pr. 57
setting
Restart cushion time
(
Pr. 58
setting)
Power supply
(R/L1, S/L2, T/L3)
Motor speed N
(r/min)
Inverter output
frequency f (Hz)
Inverter output
voltage E (V)
* The output shut off timing differs according to the load condition.
*
REMARKS
This system stores the output frequency and
rotation direction prior to an instantaneous power
failure and restart using the stored value.
Therefore, if the instantaneous power failure time
exceeds 0.2s and the stored value cannot be
retained, the inverter starts at
Pr. 13
Starting
frequency
(initial value = 0.5Hz) in the starting
direction upon power restoration.
Instantaneous (power failure) time
Power supply
(R/L1, S/L2, T/L3)
Motor speed N
(r/min)
Inverter output
frequency f (Hz)
Inverter output
voltage E (V)
Coasting time
(
Pr. 57
)
Speed
detection time
+
Acceleration time
at a restart
(
Pr. 611
setting)
*
* The output shut off timing differs
according to the load condition.
Restart cushion time
(
Pr. 58
setting)
: the rotation direction is detected.
×
: the rotation direction is not detected.
Pr. 299
Setting
Pr. 78
Setting
0
1
2
9999
×
×
0 (initial value)
×
×
×
1
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...