Monitor display and monitor output signal
(2) How to calibrate the terminal FM when using the operation panel
Operation Display
1.
Confirm the operation status indicator and
operation mode indicator
(When
Pr. 54
= 1)
2.
Press
to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously appears.)
3.
Turn
until
appears.
4.
Press
to display
.
5.
Turn
until
appears.
Set to
C0 FM terminal calibration.
6.
Press
to enable setting.
7.
If the inverter is at a stop, press the
key
to start the inverter.
(Motor needs not be connected.)
8.
Turn
to adjust the indicator needle to the
desired position.
Analog indicator
9.
Press
.
Setting is complete.
Flicker...Parameter setting complete!!
Turn
to read another parameter.
Press
to return to the
indication (step 4).
Press
twice to show the next parameter (
).
REMARKS
Calibration can also be made for External operation. Set the frequency in the External operation mode, and make calibration in
the above procedure.
Calibration can be made even during operation.
For operation from the parameter unit (FR-PU04/FR-PU07),
refer to the Instruction Manual
of the parameter unit.
Parameters referred to
Pr. 54 FM terminal function selection
Pr. 55 Frequency monitoring reference
Pr. 56 Current monitoring reference
C0 to C25 settings
are enabled.
The monitor set to
Pr. 54
FM terminal function selection
is displayed.
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...