Communication operation and setting
(3) Stop operation selection at occurrence of communication fault
(Pr. 502)
Stop operation when retry count exceeds (Mitsubishi inverter protocol only) or signal loss detection error occurs can be selected.
Operation at fault occurrence
Operation at fault removal
Pr. 502
Setting
Operation
Indication
Fault Output
0 (initial value)
Coasts to stop
E. PUE lit
Provided
1
Decelerates to stop
E. PUE lit after stop
Provided after stop
2
Not provided
Pr.502
Setting
Operation
Indication
Fault Output
0 (initial value)
Kept stopped
E. PUE
Kept provided
1
2
Automatic restart functions
Normal display
Not provided
Pr. 502
setting "0" (initial value)
Pr. 502
setting "1"
Pr. 502
setting "2"
REMARKS
The fault output indicates fault output signal (ALM signal) or alarm bit output.
When the setting was made to provide a fault output, the fault description is stored into the faults history. (The fault description
is written to the faults history when a fault output is provided.)
When no fault output is provided, the fault record overwrites the fault indication of the faults history temporarily, but is not
stored.
After the fault is removed, the fault indication returns to the ordinary monitor, and the faults history returns to the preceding fault
indication.
When the
Pr. 502
setting is "1 or 2", the deceleration time is the ordinary deceleration time setting (e.g.
Pr. 8, Pr. 44, Pr. 45
). In
addition, acceleration time for restart is the normal acceleration time (e.g.
Pr. 7, Pr. 44
).
When "2" is set in
Pr. 502
, run command/speed command at restart follows the command before an fault occurrence.
When "2" is set in
Pr. 502
at occurrence of a communication error and the error is removed during deceleration, the inverter
accelerates again at that point.
Parameters referred to
Pr. 7 Acceleration time, Pr. 8 Deceleration time
Pr. 190, Pr. 192, Pr. 197 (output terminal function selection)
Time
Communication
fault
Output frequency
Fault display
(E.PUE)
Fault output
(ALM)
ON
OFF
OFF
Display
ON
OFF
Motor coasting
Fault occurrence
Fault removal
Time
Communication
fault
Output frequency
Fault display
(E.PUE)
Fault output
(ALM)
ON
OFF
OFF
Display
ON
OFF
Decelerates to stop
Fault occurrence
Fault removal
Time
Communication
fault
Output frequency
Fault display
(E.PUE)
Fault output
(ALM)
ON
OFF
OFF
Display
OFF
Decelerates
to stop
Fault occurrence
Fault removal
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...