Operation selection at power failure and instantaneous power failure
Restart operation at every start
When
Pr. 162
= "10 or 11", automatic restart operation is also performed every start, in addition to the automatic restart
after instantaneous power failure.
When
Pr. 162
= "0", automatic restart operation is performed at the first start after power
supply ON, but not performed at the second time or later.
Automatic restart operation selection of MRS (X10) signal (When
Pr. 162
= "0, 1")
Restart operation after turning MRS (X10) signal ON then OFF using
Pr. 30
can be selected as in the table below. When
automatic restart after instantaneous power failure is selected while using the high power factor converter (FR-HC),
normally set "2" in
Pr. 30
.
(2) Restart coasting time
(Pr. 57)
Coasting time is the time from when the motor speed is detected until automatic restart control is started.
Set
Pr. 57
to "0" to perform automatic restart operation.
The coasting time is automatically set to the value below. Generally this setting will pose no problems.
1.5K or lower.... 1s
2.2K to 7.5K ..... 2s
11K and 15K..... 3s
Operation may not be performed well depending on the magnitude of the moment of inertia (J) of the load or running
frequency. Adjust the coasting time between 0.1s and 5s according to the load specifications.
(3) Restart cushion time
(Pr. 58)
Cushion time is the length of time taken to raise the voltage appropriate to detected motor speed (output frequency prior to
instantaneous power failure when
Pr. 162
= "1, 11") from 0V.
Normally the initial value need not be changed for operation, but adjust it according to the magnitude of the moment of
inertia (J) of the load or torque.
(4) Automatic restart operation adjustment
(Pr. 165, Pr. 611)
Using
Pr. 165
, you can set the stall prevention operation level at a restart.
Using
Pr. 611
, you can set the acceleration time until
Pr. 20 Acceleration/deceleration reference frequency
is reached when
automatic restart operation is performed besides the normal acceleration time.
NOTE
When automatic restart operation after instantaneous power failure is activated while the motor is running at a low speed (less
than 10Hz), the motor restarts in the direction prior to instantaneous power failure without detecting the rotation direction (
Pr.
299
Rotation direction detection selection at restarting
= "1").
If the frequency search result exceeds the set frequency, the output frequency is limited at the set frequency.
When the wiring length exceeds below, select without frequency search (
Pr. 162
= "1, 11").
Pr. 30
Setting
Operation after MRS and X10 Signal Turns OFF, ON, then OFF
0, 1
Start at the
Pr. 13 Starting frequency
.
2
Restart operation (Starts at the coasting speed)
REMARKS
When output is shut off using terminal S1 and S2, the inverter restarts in the same way as when output is shut off by MRS (X10)
signal.
Motor capacity
0.1kW
0.2kW
0.4kW or higher
Wiring length
20m
50m
100m
Voltage
100%
Pr. 58
Time
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...