142
Operation selection at power failure and instantaneous power failure
4) If offline auto tuning ended in error (see the table below), frequency search gain are not set.
Perform an inverter reset and restart tuning.
5) When tuning is ended forcibly by pressing
or turning OFF the start signal (STF or STR) during tuning, offline
auto tuning does not end properly. (The frequency search gain have not been set.)
Perform an inverter reset and restart tuning.
6) When using the motor corresponding to the following specifications and conditions, reset
Pr.9 Electronic thermal O/L
relay
as below after tuning is completed.
a) When the rated power specifications of the motor is 200/220V(400/440V) 60Hz, set 1.1 times rated motor current
value in
Pr.9
.
b) When performing motor protection from overheat using a PTC thermistor or motor with temperature detector such
as Klixon, set "0" (motor overheat protection by the inverter is invalid) in
Pr.9
.
Error
Display
Error Cause
Remedy
8
Forced end
Set "21" in
Pr. 96
and perform tuning again.
9
Inverter protective function operation
Make setting again.
91
Current limit (stall prevention) function was activated.
Set "1" in
Pr. 156
.
92
Converter output voltage reached 75% of rated value.
Check for fluctuation of power supply voltage.
93
Calculation error
A motor is not connected.
Check the motor wiring and make setting again.
Set the rated current of the motor in
Pr. 9
.
NOTE
The frequency search gain measured once in the offline auto tuning are stored as parameters and their data are held
until the offline auto tuning is performed again.
An instantaneous power failure occurring during tuning will result in a tuning error.
After power is restored, the inverter goes into the normal operation mode. Therefore, when STF (STR) signal is ON,
the motor runs in the forward (reverse) rotation.
Any alarm occurring during tuning is handled as in the ordinary mode. Note that if a fault retry has been set, retry is
ignored.
The set frequency monitor displayed during the offline auto tuning is 0Hz.
Changing the terminal assignment using
Pr.178 to Pr.182 (input terminal function selection)
may affect the other functions.
Set parameters after confirming the function of each terminal.
The SU and FU signals are not output during a restart. These are output after the restart cushion time has elapsed.
Automatic restart operation will also be performed after a reset or when a retry is made by the retry function.
CAUTION
When automatic restart after instantaneous power failure has been selected, the motor and machine will start
suddenly (after the reset time has elapsed) after occurrence of an instantaneous power failure.
Stay away from the motor and machine.
When you have selected automatic restart after instantaneous power failure function, apply in easily visible
places the CAUTION stickers supplied to the Instruction Manual (Basic).
When the start signal is turned OFF or
is pressed during the restart cushion time after instantaneous
power failure, deceleration starts after
Pr. 58 Restart cushion time
has elapsed.
Parameters referred to
Pr. 7 Acceleration time
Pr. 13 Starting frequency
Pr. 65, Pr. 67 to Pr. 69 Retry function
Pr. 71 Applied motor
Pr. 78 Reverse rotation prevention selection
Pr. 79 Operation mode selection
Pr. 178 to Pr. 182 (input terminal function selection)
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...