Selection of operation mode and operation location
4.18 Selection of operation mode and operation location
4.18.1 Operation mode selection (Pr. 79)
Purpose
Parameter that should be Set
Refer to Page
Operation mode selection
Operation mode selection
Pr. 79
Started in Network operation mode Operation mode at power-on
Pr. 79, Pr. 340
Selection of operation location
Operation command source and
speed command source during
communication operation, selection
of operation location
Pr. 338, Pr. 339
Pr. 551
Used to select the operation mode of the inverter.
Mode can be changed as desired among operation using external command signals (External operation), operation
from the operation panel and PU (FR-PU07/FR-PU04) (PU operation), combined operation of PU operation and
External operation (External/PU combined operation), and Network operation (when RS-485 communication is used).
Parameter
Number
Name
Initial
Value
Setting
Range
Description
LED Indication
:OFF
:ON
79
Operation
mode
selection
0
0
Use External/PU switchover mode (
) to switch between the
PU and External operation mode.
At power ON, the inverter is in the External operation mode.
PU operation mode
External operation
mode
NET operation mode
1
Fixed to PU operation mode
PU operation mode
2
Fixed to External operation mode
Operation can be performed by switching between the external
and NET operation mode.
External operation
mode
NET operation mode
3
External/PU combined operation mode 1
External/PU
combined operation
mode
Frequency command
Start command
Operation panel and PU (FR-
PU04/FR-PU07) setting or
external signal input (multi-speed
setting, across terminals 4-5 (valid
when AU signal turns ON)).
∗
External signal input
(terminal STF, STR)
4
External/PU combined operation mode 2
Frequency command
Start command
External signal input
(terminal 2, 4, JOG, multi-speed
selection, etc.)
Enter from
of the operation
panel and
and
of the
PU (FR-PU04/FR-PU07)
6
Switchover mode
Switchover among PU operation, External operation, and NET
operation is available while keeping the same operation status.
PU operation mode
External operation
mode
NET operation mode
7
External operation mode (PU operation interlock)
X12 signal ON
Operation mode can be switched to the PU operation mode.
(output stop during External operation)
X12 signal OFF
Operation mode can not be switched to the PU operation mode.
This parameter allows its setting to be changed in any operation mode even if "0 (initial value) or 1" is set in
Pr. 77 Parameter write selection
.
∗
The priorities of the frequency commands when
Pr. 79
= "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog input (AU)
> digital input from the operation panel".
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...