Connection of stand-alone option unit
It is recommended to configure a sequence, which shuts off power in the input side of the inverter by the external thermal
relay as shown below, to prevent overheat and burnout of the brake resistor (MRS type, MYS type) and high duty brake
resistor (FR-ABR) in case the regenerative brake transistor is damaged. (The brake resistor can not be connected to the 0.1K
and 0.2K.)
∗1
Refer to the table below for the type number of each capacity of thermal relay and the diagram below for the connection.
(Always install a thermal relay when using a brake resistor whose capacity is 11K or higher.)
∗2
When the power supply is 400V class, install a step-down transformer.
Power
Supply
Voltage
Brake Resistor
Thermal Relay Type
(Mitsubishi product)
Contact Rating
100V,
200V
MRS120W200
TH-N20CXHZ-0.7A
110VAC 5A,
220VAC 2A(AC11 class)
110VDC 0.5A,
220VDC 0.25A(DC11 class)
MRS120W100
TH-N20CXHZ-1.3A
MRS120W60
TH-N20CXHZ-2.1A
MRS120W40
TH-N20CXHZ-3.6A
MYS220W50
(two units in parallel)
TH-N20CXHZ-5A
Power
Supply
Voltage
High-duty
Brake Resistor
Thermal Relay Type
(Mitsubishi product)
Contact Rating
100V,
200V
FR-ABR-0.4K
TH-N20CXHZ-0.7A
110VAC 5A,
220VAC 2A(AC11 class)
110VDC 0.5A,
220VDC 0.25A(DC11 class)
FR-ABR-0.75K
TH-N20CXHZ-1.3A
FR-ABR-2.2K
TH-N20CXHZ-2.1A
FR-ABR-3.7K
TH-N20CXHZ-3.6A
FR-ABR-5.5K
TH-N20CXHZ-5A
FR-ABR-7.5K
TH-N20CXHZ-6.6A
FR-ABR-11K
TH-N20CXHZ-11A
FR-ABR-15K
TH-N20CXHZ-11A
400V
FR-ABR-H0.4K
TH-N20CXHZ-0.24A
FR-ABR-H0.75K
TH-N20CXHZ-0.35A
FR-ABR-H1.5K
TH-N20CXHZ-0.9A
FR-ABR-H2.2K
TH-N20CXHZ-1.3A
FR-ABR-H3.7K
TH-N20CXHZ-2.1A
FR-ABR-H5.5K
TH-N20CXHZ-2.5A
FR-ABR-H7.5K
TH-N20CXHZ-3.6A
FR-ABR-H11K
TH-N20CXHZ-6.6A
FR-ABR-H15K
TH-N20CXHZ-6.6A
NOTE
The brake resistor connected should only be the dedicated brake resistor.
Perform wiring and operation according to the Instruction Manual of each option unit.
Brake resistor can not be used with the brake unit, high power factor converter, power supply regeneration converter,
etc.
Do not use the brake resistor (MRS type, MYS type) with a lead wire extended.
Do not connect a resistor directly to terminals P/+ and N/-. This could cause a fire.
MC
Inverter
MC
R
PR
P/+
S/L2
T/L3
R/L1
OFF
ON
OCR
Contact
Power supply
F
<Example 1>
MC
High-duty brake
resistor (FR-ABR)
T
Thermal relay
(OCR) (*1)
Inverter
MC
R
PR
P/+
S/L2
T/L3
R/L1
OFF
ON
B
C
Power supply
F
<Example 2>
MC
High-duty brake
resistor (FR-ABR)
OCR
Contact
T
MC
Thermal relay
(OCR) (*1)
To the inverter
terminal P/+
To a resistor
TH-N20
1/L
1
5/L
3
2/T
1
6/T
3
Содержание FR-D710W-0.1K
Страница 45: ...36 MEMO ...
Страница 61: ...52 MEMO ...
Страница 254: ...252 MEMO ...
Страница 296: ...294 MEMO ...
Страница 297: ...295 APPENDIX This chapter provides the APPENDIX of this product Always read the instructions before using the equipment ...
Страница 308: ...4 4 BCN C22005 652 MEMO bcnc22005652 fm 4 ページ 2013年12月26日 木曜日 午後12時58分 ...
Страница 312: ...4 4 BCN C22005 689 MEMO ...